Define your own control word format

The mappable data word NetWordIN1 is available for implementing a separate control word format.
 
Details
Designation
Parameter
Associated mapping entry *
Further information
NetWordIN1
0x40080110
The functions that are to be triggered via bits 0 ... 15 of the NetWordIN1 data word are defined in 0x400E:001 ... 0x400E:016.
* A mapping entry consists of index, subindex and data length in bits of the parameter to be mapped.
General information about the process of data mapping can be found in the chapter of the same name for the corresponding network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x4008:001
Process input words: NetWordIN1
0x0000 ... [0x0000] ... 0xFFFF
Mappable data word for flexible control of the inverter via network.
Bit 0
Mapping bit 0
Assignment of the function: 0x400E:001
Bit 1
Mapping bit 1
Assignment of the function: 0x400E:002
Bit 2
Mapping bit 2
Assignment of the function: 0x400E:003
Bit 3
Mapping bit 3
Assignment of the function: 0x400E:004
Bit 4
Mapping bit 4
Assignment of the function: 0x400E:005
Bit 5
Mapping bit 5
Assignment of the function: 0x400E:006
Bit 6
Mapping bit 6
Assignment of the function: 0x400E:007
Bit 7
Mapping bit 7
Assignment of the function: 0x400E:008
Bit 8
Mapping bit 8
Assignment of the function: 0x400E:009
Bit 9
Mapping bit 9
Assignment of the function: 0x400E:010
Bit 10
Mapping bit 10
Assignment of the function: 0x400E:011
Bit 11
Mapping bit 11
Assignment of the function: 0x400E:012
Bit 12
Mapping bit 12
Assignment of the function: 0x400E:013
Alternatively, this mapping bit can be used for controlling the digital outputs.
Assignment of the digital outputs:
–
Digital output 1: 0x2634:002 / selection [30]
 
Note!
Do not assign the mapping bit to a function and a digital output at the same time. A double assignment can cause an unpredictable drive behavior!
Bit 13
Mapping bit 13
Assignment of the function: 0x400E:014
Alternatively, this mapping bit can be used for controlling the digital outputs.
Assignment of the digital outputs:
–
Digital output 1: 0x2634:002 / selection [31]
 
Note!
Do not assign the mapping bit to a function and a digital output at the same time. A double assignment can cause an unpredictable drive behavior!
Bit 14
Mapping bit 14
Assignment of the function: 0x400E:015
Alternatively, this mapping bit can be used for controlling the digital outputs.
Assignment of the digital outputs:
–
Digital output 1: 0x2634:002 / selection [32]
 
Note!
Do not assign the mapping bit to a function and a digital output at the same time. A double assignment can cause an unpredictable drive behavior!
Bit 15
Mapping bit 15
Assignment of the function: 0x400E:016
Alternatively, this mapping bit can be used for controlling the digital outputs.
Assignment of the digital outputs:
–
Digital output 1: 0x2634:002 / selection [33]
 
Note!
Do not assign the mapping bit to a function and a digital output at the same time. A double assignment can cause an unpredictable drive behavior!
0x400E:001
NetWordIN1 function: Bit 0
–
Setting can only be changed if the inverter is disabled.
 
Definition of the function that is to be triggered via bit  0 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
1
Disable inverter
Trigger bit = 0-1 edge: The inverter is disabled.
Trigger bit = 0: The inverter is enabled (unless there is another cause for inverter disable).
Notes:
–
In all device states, a 0-1 edge causes an immediate change to the inhibited state with one exception: If the inverter is in the error status and the error condition still exists, the inverter remains in the error status.
 
–
Changing to the disabled state causes an immediate stop of the motor, regardless of the stop method set in 0x2838:003. The motor coasts down as a function of the mass inertia of the machine.
 
–
In the disabled state, the motor cannot be started.
 
–
After the inverter disable is deactivated, a renewed start command is required to restart the motor.
 
–
The cause(s) that are active for the disabled state are shown in 0x282A:001.
 
2
Stopping
Trigger bit = 1: Motor is stopped.
Trigger bit = 0: No action / Deactivate stop again.
Notes:
–
The stop method can be selected in 0x2838:003.
 
3
Activate quick stop
Trigger bit = 1: "Quick stop" function activated.
Trigger bit = 0: no action / deactivate function again.
Notes:
–
The "Quick stop" function brings the motor to a standstill within the deceleration time set in 0x291C.
 
–
The "Quick stop" function has a higher priority than the "Run" function.
 
4
Reset error
Trigger bit = 0-1 edge: Active error is reset (acknowledged) if the error condition is not active anymore and the error is resettable.
Trigger bit = 0: No action.
Notes:
–
After resetting the error, a new enable/start command is required to restart the motor.
 
5
Activate DC braking
Trigger bit = 1: "DC braking" function activated.
Trigger bit = 0: no action / deactivate function again.
8
Run forward (CW)
Trigger bit = 0-1 edge: Motor is started in forward rotating direction (CW).
Trigger bit = 1-0 edge: Motor is stopped again.
Notes:
–
The stop method can be selected in 0x2838:003.
 
–
In the case of a bipolar setpoint selection (e.g 
±
10 V), the function is executed irrespective of the rotating direction. The rotating direction is determined by the sign of the setpoint.
 
–
The function also serves to realise an automatic start after switch-on. Start behavior 
 
–
The "Reverse rotational direction [13]" function can be used in connection with this function.
 
9
Run reverse (CCW)
Trigger bit = 0-1 edge: Motor is started in the reverse rotating direction (CCW).
Trigger bit = 1-0 edge: Motor is stopped again.
Notes:
–
The stop method can be selected in 0x2838:003.
 
–
In the case of a bipolar setpoint selection (e.g 
±
10 V), the function is executed irrespective of the rotating direction. The rotating direction is determined by the sign of the setpoint.
 
–
The function also serves to realise an automatic start after switch-on. Start behavior 
 
–
The "Reverse rotational direction [13]" function can be used in connection with this function.
 
13
Reverse rotational direction
Trigger bit = 1: the setpoint specified is inverted (i. e. the sign is inverted).
Trigger bit = 0: no action / deactivate function again.
14
Activate AI1 setpoint
Trigger bit = 1: analog input 1 is used as setpoint source (if the trigger bit assigned has the highest setpoint priority).
Trigger bit = 0: no action / deactivate function again.
15
Activate AI2 setpoint
Trigger bit = 1: analog input 2 is used as setpoint source (if the trigger bit assigned has the highest setpoint priority).
Trigger bit = 0: no action / deactivate function again.
17
Activate network setpoint
Trigger bit = 1: the network is used as setpoint source (if the trigger bit assigned has the highest setpoint priority).
Trigger bit = 0: no action / deactivate function again.
18
Activate preset (bit 0)
Selection bits for bit coded selection and activation of a parameterised setpoint (preset).
19
Activate preset (bit 1)
20
Activate preset (bit 2)
21
Activate preset (bit 3)
39
Activate ramp 2
Trigger bit = 1: activate acceleration time 2 and deceleration time 2 manually.
Trigger bit = 0: no action / deactivate function again.
40
Load parameter set
Trigger bit = 0-1 edge: parameter change-over to the value set selected via "Select parameter set (bit 0)" and "Select parameter set (bit 1)".
Trigger bit = 0: no action.
Notes:
–
The activation method for the "Parameter change-over" function can be selected in 0x4046.
 
41
Select parameter set (bit 0)
Selection bits for the "Parameter change-over" function.
42
Select parameter set (bit 1)
43
Activate fault 1
Trigger bit = 1: Trigger user-defined error 1.
Trigger bit = 0: no action.
Notes:
–
After the error is triggered, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
 
Associated error code:
–
25249 | 0x62A1 - Network: user fault 1
 
44
Activate fault 2
Trigger bit = 1: Trigger user-defined error 2.
Trigger bit = 0: no action.
Notes:
–
After the error is triggered, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
 
Associated error code:
–
25250 | 0x62A2 - Network: user fault 2
 
45
Disable PID controlling
Trigger bit = 1: If PID control is activated, ignore PID control and drive the motor in speed-controlled manner.
Trigger bit = 0: If PID control is activated, drive the motor with PID control.
Notes:
–
The PID control can be activated in 0x4020:001.
 
46
Set PID output to 0
Trigger bit = 1: If PID control is activated, I component and the output of the PID controller are set to 0 and the internal control algorithm is stopped. The PID control remains active.
Trigger bit = 0: No action / deactivate function again.
47
Inhibit PID I-component
Trigger bit = 1: If the PID control is activated, the I component of the PID controller is set to 0 and the integration process is stopped.
Trigger bit = 0: No action / deactivate function again.
48
Activate PID influence ramp
Trigger bit = 1: the influence of the process controller is shown by means of a ramp.
Trigger bit = 0 or not connected: the influence of the process controller is shown by means of a ramp.
Notes:
–
The influence of the process controller is always active (not only when PID control is activated).
 
–
Acceleration time for showing the influence of the process controller can be set in 0x404C:001.
 
–
Deceleration time for hiding the influence of the process controller can be set in 0x404C:002.
 
49
Release holding brake
Trigger bit = 1: Release holding brake manually.
Trigger bit = 0: No action.
Notes:
–
The manually triggered "Release holding brake" command has a direct impact on the "Release holding brake [115]" trigger. Thus, the holding brake can be manually released if the power section is switched off.
 
–
The responsibility for a manual release of the holding brake has the external trigger source for the "Release holding brake" command.
 
54
Position counter reset
Trigger bit = 1: Reset position counter manually.
Trigger bit = 0: No action.
60
Enable operation
61
Source of flying homing
Control signals for the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
63
Manual jog positive
64
Manual jog negative
65
Halt
66
Start homing
67
Reset home position
68
Abort
69
Activate velocity override
70
Profile number (bit 0)
71
Profile number (bit 1)
72
Profile number (bit 2)
73
Profile number (bit 3)
74
Start
75
Resume
76
Deactivate touch probe
77
Activate external set position
0x400E:002
NetWordIN1 function: Bit 1
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  1 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:003
NetWordIN1 function: Bit 2
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  2 of the mappable NetWordIN1 data word.
3
Activate quick stop
Trigger bit = 1: "Quick stop" function activated.
Trigger bit = 0: no action / deactivate function again.
Notes:
–
The "Quick stop" function brings the motor to a standstill within the deceleration time set in 0x291C.
 
–
The "Quick stop" function has a higher priority than the "Run" function.
 
0x400E:004
NetWordIN1 function: Bit 3
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  3 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:005
NetWordIN1 function: Bit 4
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  4 of the mappable NetWordIN1 data word.
8
Run forward (CW)
Trigger bit = 0-1 edge: Motor is started in forward rotating direction (CW).
Trigger bit = 1-0 edge: Motor is stopped again.
Notes:
–
The stop method can be selected in 0x2838:003.
 
–
In the case of a bipolar setpoint selection (e.g 
±
10 V), the function is executed irrespective of the rotating direction. The rotating direction is determined by the sign of the setpoint.
 
–
The function also serves to realise an automatic start after switch-on. Start behavior 
 
–
The "Reverse rotational direction [13]" function can be used in connection with this function.
 
0x400E:006
NetWordIN1 function: Bit 5
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  5 of the mappable NetWordIN1 data word.
18
Activate preset (bit 0)
Selection bits for bit coded selection and activation of a parameterised setpoint (preset).
0x400E:007
NetWordIN1 function: Bit 6
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  6 of the mappable NetWordIN1 data word.
19
Activate preset (bit 1)
Selection bits for bit coded selection and activation of a parameterised setpoint (preset).
0x400E:008
NetWordIN1 function: Bit 7
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  7 of the mappable NetWordIN1 data word.
4
Reset error
Trigger bit = 0-1 edge: Active error is reset (acknowledged) if the error condition is not active anymore and the error is resettable.
Trigger bit = 0: No action.
Notes:
–
After resetting the error, a new enable/start command is required to restart the motor.
 
0x400E:009
NetWordIN1 function: Bit 8
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  8 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:010
NetWordIN1 function: Bit 9
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  9 of the mappable NetWordIN1 data word.
5
Activate DC braking
Trigger bit = 1: "DC braking" function activated.
Trigger bit = 0: no action / deactivate function again.
0x400E:011
NetWordIN1 function: Bit 10
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  10 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:012
NetWordIN1 function: Bit 11
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  11 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:013
NetWordIN1 function: Bit 12
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  12 of the mappable NetWordIN1 data word.
13
Reverse rotational direction
Trigger bit = 1: the setpoint specified is inverted (i. e. the sign is inverted).
Trigger bit = 0: no action / deactivate function again.
0x400E:014
NetWordIN1 function: Bit 13
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  13 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:015
NetWordIN1 function: Bit 14
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  14 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.
0x400E:016
NetWordIN1 function: Bit 15
–
Setting can only be changed if the inverter is disabled.
 
–
For further possible settings, see parameter 0x400E:001.
 
Definition of the function that is to be triggered via bit  15 of the mappable NetWordIN1 data word.
0
Not active
Trigger bit without any function.