Define your own status word format

The mappable data word NetWordOUT1 is available for implementing a separate status word format.
 
Details
Designation
Parameter
Associated mapping entry *
Further information
NetWordOUT1
0x400A0110
The triggers for bits 0 ... 15 of the NetWordOUT1 data word are defined in 0x2634:010 ... 0x2634:025.
* A mapping entry consists of index, subindex and data length in bits of the parameter to be mapped.
General information about the process of data mapping can be found in the chapter of the same name for the corresponding network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2634:010
Digital outputs function: NetWordOUT1 - bit 0
Assignment of a trigger to bit 0 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
1
Constant TRUE
Trigger is constantly TRUE.
11
Digital input 1
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
12
Digital input 2
State of X3/DI2, taking an inversion set in 0x2632:002 into consideration.
13
Digital input 3
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.
14
Digital input 4
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
15
Digital input 5
State of X3/DI5, taking an inversion set in 0x2632:005 into consideration.
16
Digital input 6
State of X3/DI6, taking an inversion set in 0x2632:006 into consideration.
17
Digital input 7
State of X3/DI7, taking an inversion set in 0x2632:007 into consideration.
18
Digital input 8
State of X3/DI8, taking an inversion set in 0x2632:008 into consideration.
30
NetWordIN1 - bit 12
State of NetWordIN1/bit 12 ... 15.
–
Display of NetWordIN1 in 0x4008:001.
 
–
For implementing an individual control word format, NetWordIN1 can be mapped to a process data input word.
 
31
NetWordIN1 - bit 13
32
NetWordIN1 - bit 14
33
NetWordIN1 - bit 15
34
NetWordIN2 - bit 0
State of NetWordIN2/bit 0 ... bit 15.
–
Display of NetWordIN2 in 0x4008:002.
 
–
For controlling the digital outputs via network, NetWordIN2 can be mapped to a process data input word.
 
35
NetWordIN2 - bit 1
36
NetWordIN2 - bit 2
37
NetWordIN2 - bit 3
38
NetWordIN2 - bit 4
39
NetWordIN2 - bit 5
40
NetWordIN2 - bit 6
41
NetWordIN2 - bit 7
42
NetWordIN2 - bit 8
43
NetWordIN2 - bit 9
44
NetWordIN2 - bit 10
45
NetWordIN2 - bit 11
46
NetWordIN2 - bit 12
47
NetWordIN2 - bit 13
48
NetWordIN2 - bit 14
49
NetWordIN2 - bit 15
50
Running
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
51
Ready for operation
TRUE if inverter is ready for operation (no error active, no STO active and DC-bus voltage ok). Otherwise FALSE.
52
Operation enabled
TRUE if inverter and start are enabled. Otherwise FALSE.
53
Stop active
TRUE if inverter is enabled and motor is not started and output frequency = 0.
54
Quick stop active
TRUE if quick stop is active. Otherwise FALSE.
55
Inverter disabled (safety)
TRUE if the integrated safety system has inhibited the inverter. Otherwise FALSE.
56
Fault active
TRUE if error is active. Otherwise FALSE.
57
Error (non-resettable) active
TRUE if non-resettable error is active. Otherwise FALSE.
58
Device warning active
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
 
–
A warning is reset automatically if the cause has been eliminated.
 
59
Device trouble active
TRUE if a fault is active. Otherwise FALSE.
–
In the event of a fault, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
 
–
Exception: In case of a serious fault, the inverter is disabled immediately. The motor has no torque (coasts).
 
–
The error state will be left automatically if the error condition is not active anymore.
 
–
The restart behaviour after trouble can be configured. Automatic restart after a fault 
 
60
Heatsink temperature warning active
TRUE if current heatsink temperature > warning threshold for temperature monitoring. Otherwise FALSE.
–
Display of the current heatsink temperature in 0x2D84:001.
 
–
Setting of the warning threshold in 0x2D84:002.
 
65
Motor PTC error active
TRUE if an error of the motor PTC has been detected. Otherwise FALSE.
–
The trigger is set irrespective of the response set in 0x2D49:002 when the motor temperature monitoring is triggered.
 
66
Flying restart circuit active
TRUE if flying restart circuit active is active. Otherwise FALSE.
67
DC braking active
TRUE if DC braking is active. Otherwise FALSE.
68
Stop command active
TRUE if delay to standstill active. Otherwise FALSE.
69
Rotational direction reversed
TRUE if output frequency is negative. Otherwise FALSE.
70
Frequency threshold exceeded
TRUE if current output frequency > frequency threshold. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
–
Setting Frequency threshold in 0x4005.
 
71
Actual speed = 0
TRUE if actual output frequency = 0 Hz (
±
0.3 Hz), irrespective of the operating mode. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
72
Setpoint speed reached
TRUE if frequency setpoint reached. Otherwise FALSE.
73
PID feedback = setpoint
TRUE if the controlled feedback variable = process controller setpoint (± in 0x404D:003 set hysteresis). Otherwise FALSE.
74
PID sleep mode active
TRUE if the inverter is in "PID sleep mode". Otherwise FALSE.
75
PID MIN alarm active
TRUE if feedback variable (with activated PID control) < MIN alarm threshold. Otherwise FALSE.
–
Setting of MIN alarm threshold in 0x404D:001.
 
76
PID MAX alarm active
TRUE if the feedback variable (with activated PID control) > MAX alarm threshold. Otherwise FALSE.
–
Setting of MAX alarm threshold in 0x404D:002.
 
77
PID MIN-MAX alarm active
TRUE if no PID alarm is active with activated PID control (MIN alarm threshold < feedback variable < MAX alarm threshold). Otherwise FALSE.
–
Setting of MIN alarm threshold in 0x404D:001.
 
–
Setting of MAX alarm threshold in 0x404D:002.
 
78
Current limit reached
TRUE if current motor current
≥
maximum current. Otherwise FALSE.
–
Display of the present motor current in 0x2D88.
 
–
Setting for the maximum current in 0x6073.
 
79
Torque limit reached
TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
–
Setting "Actual positive torque limit" in 0x2949:003.
 
–
Setting "Actual negative torque limit" in 0x2949:004.
 
81
Error of analog input 1 active
TRUE if the monitoring of the input signal at the analog input 1 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2636:008
 
–
Monitoring condition 0x2636:009
 
The setting of the Error response in 0x2636:010 has no effect on this trigger.
82
Error of analog input 2 active
TRUE if the monitoring of the input signal at the analog input 2 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2637:008
 
–
Monitoring condition 0x2637:009
 
The setting of the Error response in 0x2637:010 has no effect on this trigger.
83
Load loss detected
TRUE if actual motor current < threshold for load loss detection after delay time of the load loss detection has elapsed. Otherwise FALSE.
–
Display of the actual current in 0x6078.
 
–
Setting Threshold in 0x4006:001.
 
–
Setting Delay time in 0x4006:002.
 
84
Heavy load monitoring
TRUE if the actual apparent current of the motor exceeds the threshold for longer than the delay time.
FALSE if the actual apparent current of the motor falls below the threshold value minus 5 % (hysteresis).
108
Parameter set 1 active
TRUE if parameter set 1 is loaded and active. Otherwise FALSE.
109
Parameter set 2 active
TRUE if parameter set 2 is loaded and active. Otherwise FALSE.
110
Parameter set 3 active
TRUE if parameter set 3 is loaded and active. Otherwise FALSE.
111
Parameter set 4 active
TRUE if parameter set 4 is loaded and active. Otherwise FALSE.
112
Parameter set load OK
TRUE after any parameter set has been loaded. Otherwise FALSE.
113
Parameter set load fail
TRUE if any of the parameter sets could not be loaded. Otherwise FALSE.
117
Motor phase failure
TRUE if a motor phase failure has been detected. Otherwise FALSE.
Note!
In the "SLSM-PSM" motor control mode, detection for motor phase failure is deactivated if HF injection is active in the low-speed range.
119
Holding brake released
TRUE, if holding brake is released. Otherwise FALSE.
120
Homing active
Status signals output by the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
 
121
Homing done
122
Manual jog active
123
Halt active
124
Motor control in limitation
125
Set position reached
126
Abort active
127
Standstill
128
Active profile (bit 1)
129
Active profile (bit 2)
130
Active profile (bit 3)
131
Active profile (bit 4)
132
Positioning profile active
133
Positioning profile done
134
Negative hardware limit switch active
135
Positive hardware limit switch active
136
Touch probe detected
137
External position active
155
STO active
TRUE if the integrated safety system has triggered the "Safe torque off (STO)" function and if the safe inputs SIA and SIB = LOW (simultaneously). Otherwise FALSE.
224
IOL1 BI1 value
Binary values received via IO-Link corresponding to the binary input configuration for the respective IO-Link port.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
225
IOL1 BI2 value
226
IOL1 BI3 value
227
IOL1 BI4 value
228
IOL1 BI5 value
229
IOL1 BI6 value
230
IOL1 BI7 value
231
IOL1 BI8 value
232
IOL2 BI1 value
233
IOL2 BI2 value
234
IOL2 BI3 value
235
IOL2 BI4 value
236
IOL2 BI5 value
237
IOL2 BI6 value
238
IOL2 BI7 value
239
IOL2 BI8 value
240
IOL3 BI1 value
241
IOL3 BI2 value
242
IOL3 BI3 value
243
IOL3 BI4 value
244
IOL3 BI5 value
245
IOL3 BI6 value
246
IOL3 BI7 value
247
IOL3 BI8 value
248
IOL4 BI1 value
249
IOL4 BI2 value
250
IOL4 BI3 value
251
IOL4 BI4 value
252
IOL4 BI5 value
253
IOL4 BI6 value
254
IOL4 BI7 value
255
IOL4 BI8 value
0x2634:011
Digital outputs function: NetWordOUT1 - bit 1
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 1 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:012
Digital outputs function: NetWordOUT1 - bit 2
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 2 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
52
Operation enabled
TRUE if inverter and start are enabled. Otherwise FALSE.
0x2634:013
Digital outputs function: NetWordOUT1 - bit 3
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 3 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
56
Fault active
TRUE if error is active. Otherwise FALSE.
0x2634:014
Digital outputs function: NetWordOUT1 - bit 4
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 4 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:015
Digital outputs function: NetWordOUT1 - bit 5
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 5 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
54
Quick stop active
TRUE if quick stop is active. Otherwise FALSE.
0x2634:016
Digital outputs function: NetWordOUT1 - bit 6
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 6 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
50
Running
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
0x2634:017
Digital outputs function: NetWordOUT1 - bit 7
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 7 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
58
Device warning active
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
 
–
A warning is reset automatically if the cause has been eliminated.
 
0x2634:018
Digital outputs function: NetWordOUT1 - bit 8
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 8 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:019
Digital outputs function: NetWordOUT1 - bit 9
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 9 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:020
Digital outputs function: NetWordOUT1 - bit 10
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 10 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
72
Setpoint speed reached
TRUE if frequency setpoint reached. Otherwise FALSE.
0x2634:021
Digital outputs function: NetWordOUT1 - bit 11
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 11 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
78
Current limit reached
TRUE if current motor current
≥
maximum current. Otherwise FALSE.
–
Display of the present motor current in 0x2D88.
 
–
Setting for the maximum current in 0x6073.
 
0x2634:022
Digital outputs function: NetWordOUT1 - bit 12
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 12 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
71
Actual speed = 0
TRUE if actual output frequency = 0 Hz (
±
0.3 Hz), irrespective of the operating mode. Otherwise FALSE.
–
Display of the current output frequency in 0x2DDD.
 
0x2634:023
Digital outputs function: NetWordOUT1 - bit 13
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 13 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
69
Rotational direction reversed
TRUE if output frequency is negative. Otherwise FALSE.
0x2634:024
Digital outputs function: NetWordOUT1 - bit 14
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 14 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:025
Digital outputs function: NetWordOUT1 - bit 15
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to bit 15 of NetWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
55
Inverter disabled (safety)
TRUE if the integrated safety system has inhibited the inverter. Otherwise FALSE.
0x2635:010
Inversion of digital outputs: NetWordOUT1.00
Inversion of bit 0 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:011
Inversion of digital outputs: NetWordOUT1.01
Inversion of bit 1 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:012
Inversion of digital outputs: NetWordOUT1.02
Inversion of bit 2 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:013
Inversion of digital outputs: NetWordOUT1.03
Inversion of bit 3 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:014
Inversion of digital outputs: NetWordOUT1.04
Inversion of bit 4 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:015
Inversion of digital outputs: NetWordOUT1.05
Inversion of bit 5 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:016
Inversion of digital outputs: NetWordOUT1.06
Inversion of bit 6 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:017
Inversion of digital outputs: NetWordOUT1.07
Inversion of bit 7 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:018
Inversion of digital outputs: NetWordOUT1.08
Inversion of bit 8 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:019
Inversion of digital outputs: NetWordOUT1.09
Inversion of bit 9 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:020
Inversion of digital outputs: NetWordOUT1.10
Inversion of bit 10 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:021
Inversion of digital outputs: NetWordOUT1.11
Inversion of bit 11 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:022
Inversion of digital outputs: NetWordOUT1.12
Inversion of bit 12 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:023
Inversion of digital outputs: NetWordOUT1.13
Inversion of bit 13 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:024
Inversion of digital outputs: NetWordOUT1.14
Inversion of bit 14 of NetWordOUT1.
0
Not inverted
1
Inverted
0x2635:025
Inversion of digital outputs: NetWordOUT1.15
Inversion of bit 15 of NetWordOUT1.
0
Not inverted
1
Inverted
0x400A:001
Process output words: NetWordOUT1
–
Read only
 
Mappable data word for the output of status messages of the inverter via network.
Bit 0
Mapping bit 0
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:010
Bit 1
Mapping bit 1
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:011
Bit 2
Mapping bit 2
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:012
Bit 3
Mapping bit 3
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:013
Bit 4
Mapping bit 4
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:014
Bit 5
Mapping bit 5
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:015
Bit 6
Mapping bit 6
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:016
Bit 7
Mapping bit 7
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:017
Bit 8
Mapping bit 8
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:018
Bit 9
Mapping bit 9
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:019
Bit 10
Mapping bit 10
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:020
Bit 11
Mapping bit 11
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:021
Bit 12
Mapping bit 12
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:022
Bit 13
Mapping bit 13
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:023
Bit 14
Mapping bit 14
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:024
Bit 15
Mapping bit 15
Mappable data word for the output of status messages of the inverter via network.
Assignment of the status message: 0x2634:025