Network selection for X396/X397
The Multi-Ethernet interface of the i550/i650 motec inverter supports the typical topologies and protocols of the following networks:
–
–
–
–
To provide the user with the expected functionality of one of these systems, the inverter is ordered for a specific network. The ordered network is then preset in the inverter (displayed in 0x231F:001).
The inverter itself has the firmware of all available networks on board and the user has the possibility to switch the inverter to another network.
Details
Switch to another network:
1.
Set network in 0x231F:005.
2.
Restart device (via Engineering Tool or 0x2022:035).
The inverter is switched to the newly selected network. All parameters associated with the old network are lost, but the drive parameters are retained.
Executing the device command "Load presets" (0x2022:001), uploading a new firmware or power cycles do not change the selected network.
Parameter