Activate network control
In order to be able to control the inverter via network, a trigger must be first assigned in 0x2631:037 to the "Activate network control" function.
–
This trigger can for instance be the constant value "TRUE" or a digital input.
–
If the assigned trigger is = TRUE, network control is activated and the motor can only be started via the network control word.
Exception: Jog operation; see chapter "Start, stop and rotating direction commands"
Exception: Jog operation; see chapter "Start, stop and rotating direction commands"
In case of an activated network control, the following functions are still active:
–
0x2631:001: Enable inverter
–
0x2631:002: Run
–
0x2631:003: Activate quick stop
–
0x2631:004: Reset error
–
0x2631:005: DC braking
–
0x2631:010: Jog forward (CW)
–
0x2631:011: Jog reverse (CCW)*
–
0x2631:037: Activate network control*
–
0x2631:043: Activate error 1
–
0x2631:044: Activate error 2
(*Not active in case of network operation in CiA402 mode 0x6060=2).
All other functions configurable via 0x2631:xxx are deactivated in case of network control.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2631:037
|
Function list: Activate network control
|
Assignment of a trigger for the "Activate network control" function.
Trigger = TRUE: Activate network control.
Trigger = FALSE: no action / deactivate network control again.
|
|
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
114
|
Network control active
|
TRUE if the network control is requested via bit 5 of the AC drive control word 0x400B:001. Otherwise FALSE.
Notes:
–
Set this selection if the network control is to be activated via bit 5 of the AC drive control word.
–
The AC drive control word can be used with any communication protocol.
|
|
Trigger list