EtherNet/IP communication monitoring

Parameter
Address
Name / setting range / [default setting]
Information
0x23A1:010
EtherNet/IP settings: Timeout
500 ... [10000] ... 65535 ms
Setting of the maximum permissible time-out for the CIP communication.
When the specified monitoring time has elapsed, the response set in 0x2859:007 is triggered in the inverter.
0x23A1:011
EtherNet/IP settings: Inactivity timeout
0 ... [120] ... 3600 s
0x2859:006
Network monitoring: Time-out explicit message
Selection of the response to time-outs during the transfer of Explicit Messages.
Associated event ID:
–
33042 | 0x8112 - Network - Time-out explicit message
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2859:007
Network monitoring: Timeout communication
Selection of the response to the time-out during the CIP communication.
The monitoring time for the CIP communication is defined in 0x23A1:010.
Associated event ID:
–
33044 | 0x8114 - Network - Overall communication time-out
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2859:001
Network monitoring: Watchdog elapsed
Selection of the response to a permanent interruption of the communication to the IO controller.
Associated event ID:
–
33168 | 0x8190 - Network - Watchdog time-out
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled