Safe parameter setting is only possible if the control electronics have an existing mains-dependent or mains-independent DC supply.
Safe parameter setting is not possible if the device is powered exclusively via the USB interface.
Safe parameter setting
Safety parameters can only be set and transferred in the »EASY Starter« and »PLC Designer« via a special parameterization dialog. This parameterization dialog is available when you select a device with integrated safety technology or a safety module.
Open parameterization dialog for safety parameters:
–
»EASY Starter«: Open the Safety parameter list tab.
–
»PLC Designer«: Open the Safety parameter set object under the axis in the device tree.
The safe parameterization is checked for plausibility.
The plausibility check rejects ambiguous or contradictory settings until they have been parameterized correctly. Only then can the parameters be saved.
Service status
Safe parameterization via the parameterization dialog for safety parameters requires the service status. The service status means:
–
Stop is active and the drive is switched to torqueless operation (STO).
–
Communication via the safety bus is active but passivated.
The service status can be activated using the »EASY Starter« or »PLC Designer«. Initializing the safety option serves to deactivate the service status.
The service status is activated if a deviation is detected in the safe parameter set on the safety option.
Password
A password is required to save a secure set of parameters.
–
The default password is "Lenze Safety."
–
The password can be changed and must be at least 6 characters long.
To change your password:
1.
Open the parameterization dialog for safety parameters:
a.
»EASY Starter«: Open the Safety parameter list tab.
b.
»PLC Designer«: In the device tree, under the axis, open the object Safety parameter set in the device tree under the axis.
2.
Click the (Change password) button and select the "Download password" command.
The "Change password" dialog box opens.
3.
Set your old and new passwords.
4.
Transfer the safety parameters to the device so that the password change takes effect.
Reset safe parameter set in the device.
The command Reset safe parameter set in the device serves to delete the safe parameter set. The safety functions must be re-parameterized after the reset. The password is reset to the preset password "Lenze Safety".
(Change password) button and select the "Download password" command.