Safety - Parameter set plausibility errors

The following table contains the detailed information about the possible plausibility errors.
The error code corresponds to the entry in 0x2115:005.
 
 
Error information 1
Error in the setting of the safe parameterization
1
If SD-In1 is deactivated, SD-In1 must not be parameterized as a source for any function.
2
If SD-In2 is deactivated, SD-In2 must not be parameterized as a source for any function.
5
If no safety bus is parameterized, no S-Bus bit may be parameterized as source for a function.
9
If SS1 is parameterized so that STO is triggered after reaching n = 0, the delay time "STO after n = 0" must be less than or equal to the stopping time.
10
If OMS is used via the S-Bus, "OMS: Function at LOW level" must be equal to "Normal operation", because a level inversion on the S-Bus has no effect.
11
If OMS is used via S-Bus, at least one stop function must also be parameterized via S-Bus to switch to the safe state in the event of bus failure.
27
If muting (MUT) is parameterized, a password must be assigned.
29
If the S-Bus is to be muted (MUT), an S-Bus must also be enabled.
30
If SD-In1 is to be muted (MUT), SD-In1 must also be enabled.
31
If SD-In2 is to be muted (MUT), SD-In2 must also be enabled.
100
Assign SD-In1-A correctly.
101
Assign SD-In1-B correctly.
102
Assign SD-In2-A correctly.
103
Assign SD-In2-B correctly.
108
Do not parameterize SD-In1 as SIL 2 if it is parameterized as SIL 3.
Do not parameterize SD-In1-A as SIL 3 if it is parameterized as SIL 2.
Do not parameterize SD-In1-B as SIL 3 if it is parameterized as SIL 2.
109
Do not parameterize SD-In2 as SIL 2 if it is paramterized as SIL 3.
Do not parameterize the SD-In2-A as SIL 3 if it is parameterized as SIL 2.
Do not parameterize the SD-In2-B as SIL 3 if it is parameterized as SIL 2.
112
If SD-In1 is enabled, SD-In1 must also be used.
113
If SD-In2 is enabled, SD-In2 must also be used.
116
If SD-In1-A is enabled, SD-In1-A must also be used.
117
If SD-In1-B is enabled, SD-In1-B must also be used.
118
If SD-In2-A is enabled, SD-In2-A must also be used.
119
If SD-In2-B is enabled, SD-In2-B must also be used.
124
The stop time for SS1 must be nonzero when the SS1 function is enabled.
125
If an absolute ramp is set for SS1, the relative ramp must be set to the default value.
126
If a relative ramp is set for SS1, the absolute ramp must be set to the default value.
127
The smoothing time must be less than the stop time when SS1 is enabled.
143
If SD-In1-A is to be muted (MUT), SD-In1-A must also be enabled.
144
If SD-In1-B is to be muted (MUT), SD-In1-B must also be enabled.
145
If SD-In2-A is to be muted (MUT), SD-In2-A must also be enabled.
146
If SD-In2-B is to be muted (MUT), SD-In2-B must also be enabled.