Monitoring

The parameters for setting network monitoring functions are described below.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x23B1:010
Modbus -TCP/IP settings: Ethernet time-out
0 ... [10] ... 65535 s
Setting of the maximum permissible time-out of the TCP communication.
When the specified monitoring time has elapsed, the response set in 0x2859:007 is triggered in the inverter.
0x23B6:001
Time-out monitoring: Time-out time
0.0 ... [2.0] ... 300.0 s
Monitoring is active if the first valid write command arrives at the Modbus client. Each further valid write/read message resets the watchdog timer.
Monitoring responds if within the time set here no valid message has been received by the Modbus client.
0x23B6:002
Time-out monitoring: Keep alive time-out time
0.0 ... [2.0] ... 300.0 s
Monitoring is active after a valid value is written into the keep alive register 0x23B6:005 via the Modbus for the first time.
Keep alive monitoring responds if no value (range 1 ... 65535) has been written into the keep alive register within the time set here.
0x23B6:005
Time-out monitoring: Keep alive register
0 ... [0] ... 65535
Time-out monitoring of the keep alive register is active after a value has been written into the keep alive register for the first time.
In order to prevent that time-out monitoring for the keep alive register responds, the keep alive register must be written as follows:
–
With a value of 1 ... 65535 and
 
–
an interval that is shorter than the time set in 0x23B6:002.
 
0x2859:008
Network monitoring: Fault response to master timeout
Selection of the response if within the time set in 0x23B6:001 no valid message has arrived at the Modbus client.
Associated event ID:
–
33046 | 0x8116 - Modbus TCP master time-out
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled
0x2859:009
Network monitoring: Fault response to keep alive timeout
Selection of the response if within the time set in 0x23B6:002 no valid message has been written into the keep alive register.
Associated event ID:
–
33047 | 0x8117 - Modbus TCP Keep Alive time-out
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled