Monitoring
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2859:012
|
Network monitoring: Response to time-out
|
Selection of the response executed if no valid messages have been received via the Modbus for a longer time than the time-out period set in 0x2326:001.
|
|
|
0
|
No response
|
||
|
11
|
Information
|
||
|
12
|
Warning
|
||
|
16
|
Trouble
|
||
|
23
|
Fault > inverter disabled
|
||
|
0x2326:001
|
Modbus monitoring: Time-out time
0.0 ... [2.0] ... 300.0 s
|
Time-out period for monitoring the message reception via Modbus.
|
|
Severity