Axis parameters
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x500A:020
|
TA axis parameter: Motion kind
–
Setting can only be changed if the inverter is disabled.
|
||
|
0
|
not defined
|
||
|
1
|
translatory
|
||
|
2
|
rotary
|
||
|
0x500A:029
|
TA axis parameter: Virtual mode
–
Setting can only be changed if the inverter is disabled.
|
With the "Virtual mode" function, the application can be tested without a connected motor. If the function is activated, the set values generated in the application are not forwarded to the drive. The actual values (e.g. position and speed) are generated from the setpoint values.
–
The kinematics parameters have no influence in virtual mode. Only the travel range and cycle length parameters are used for the machine measuring system.
|
|
|
0
|
Inactive
|
||
|
1
|
Active
|
||
|
0x500A:030
|
TA axis parameter: Travel range
–
Setting can only be changed if the inverter is disabled.
|
Kinematics parameters
–
The kinematics parameters describe, among other things, the motor side with regard to the mechanics used.
|
|
|
0
|
Modulo
|
||
|
1
|
Limited
|
||
|
0x500A:031
|
TA axis parameter: Cycle length
0.0001 ... [360.0000] ... 214748.3647 Unit
–
Setting can only be changed if the inverter is disabled.
|
||
|
0x500A:032
|
TA axis parameter: Feed constant
0.0001 ... [360.0000] ... 214748.3647
–
Setting can only be changed if the inverter is disabled.
|
||
|
0x500A:033
|
TA axis parameter: Gearbox factor - nominator
1 ... [1] ... 4294967295
–
Setting can only be changed if the inverter is disabled.
|
||
|
0x500A:034
|
TA axis parameter: Gearbox factor - denominator
1 ... [1] ... 4294967295
–
Setting can only be changed if the inverter is disabled.
|
||
|
0x500A:045
|
TA axis parameter: Max. velocity
0.0000 ... [0.0000] ... 214748.3647 unit/s
|
Maximum values for profile parameters.
|
|
|
0x500A:046
|
TA axis parameter: Max. acceleration
0.00 ... [0.00] ... 21474836.47 unit/s²
|
||
|
0x500A:047
|
TA axis parameter: Max. jerk
0.00 ... [0.00] ... 21474836.47 unit/s³
|
||
|
0x500A:050
|
TA axis parameter: Enable software position limits
|
The adjustable software limit positions are used to limit the travel range on the software side and prevent travel commands from being executed that would result in the permissible travel range being exceeded.
–
If the software limit positions are enabled and these are reached using the "Manual operation" function, for example, the movement is stopped, i.e. the axis is brought to a standstill using the "Stop" function. The software limit positions can then be released in the direction of the permitted travel range.
–
In the event of an error, the reaction set in 0x500A:105 is triggered (e.g. output of a warning).
|
|
|
0
|
Inactive
|
||
|
1
|
Active
|
||
|
0x500A:051
|
TA axis parameter: Software position limit positive
-214748.3648 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:052
|
TA axis parameter: Software position limit negative
-214748.3648 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:054
|
TA axis parameter: Following error monitoring
|
The following error is the difference between the setpoint position and the actual position. The following error should ideally be "0". If the position control is set optimally, only a minimum following error is formed. The following error is regulated dynamically and does not increase continuously.
However, certain processes require that the following error does not exceed a certain limit value, as otherwise the system part will not reach the defined target position in time, for example. For such processes, two limit values for the following error can be set and activated.
With active monitoring:
–
If the first limit value ("warning threshold") is exceeded, a warning is displayed. However, the current movement of the axis is not interrupted.
–
If the second limit value ("error threshold") is exceeded, the reaction set for this monitoring in 0x500A:059 is triggered.
|
|
|
0
|
Inactive
|
||
|
1
|
Active
|
||
|
0x500A:055
|
TA axis parameter: Following error: Warning threshold
0.0000 ... [180.0000] ... 214748.3647 Unit
|
||
|
0x500A:056
|
TA axis parameter: Following error: Error threshold
0.0000 ... [360.0000] ... 214748.3647 Unit
|
||
|
0x500A:057
|
TA axis parameter: Actual following error
–
Read only: x.xxxx Unit
|
||
|
0x500A:058
|
TA axis parameter: Maximum following error
–
Read only: x.xxxx Unit
|
||
|
0x500A:059
|
TA axis parameter: Response to following error
|
||
|
12
|
Warning
|
||
|
23
|
Fault
|
||
|
0x500A:070
|
TA axis parameter: Homing mode
|
||
|
-2
|
CwTorqueLimit
|
||
|
-1
|
CcwTorqueLimit
|
||
|
0
|
SetPositionDirect
|
||
|
1
|
CcwLimitSwitchCwTP
|
||
|
2
|
CwLimitSwitchCcwTP
|
||
|
3
|
CwRpCcwRnTP
|
||
|
5
|
CcwRpCwRnTP
|
||
|
17
|
CcwLimitSwitch
|
||
|
18
|
CwLimitSwitch
|
||
|
19
|
CwRpCcwRn
|
||
|
21
|
CcwRpCwRn
|
||
|
33
|
CcwTP
|
||
|
34
|
CwTP
|
||
|
0x500A:071
|
TA axis parameter: Action after "Home position detected"
|
||
|
0
|
Stop positioning
|
||
|
1
|
Relative positioning
|
||
|
2
|
Absolute positioning
|
||
|
0x500A:072
|
TA axis parameter: Homing: Target position
-214748.3648 ... [0.0000] ... 214748.3647 Unit
|
Profile parameters for the "Homing" function.
|
|
|
0x500A:073
|
TA axis parameter: Homing: Velocity 1
0.0000 ... [360.0000] ... 214748.3647 unit/s
|
||
|
0x500A:074
|
TA axis parameter: Homing: Velocity 2
0.0000 ... [0.0000] ... 214748.3647 unit/s
|
||
|
0x500A:075
|
TA axis parameter: Homing: Acceleration 1
0.00 ... [720.00] ... 21474836.47 unit/s²
|
||
|
0x500A:076
|
TA axis parameter: Homing: Acceleration 2
0.00 ... [360.00] ... 21474836.47 unit/s²
|
||
|
0x500A:077
|
TA axis parameter: Homing: Jerk
0.00 ... [7200.00] ... 21474836.47 unit/s³
|
||
|
0x500A:078
|
TA axis parameter: Homing: Torque limit
0.00 ... [0.10] ... 21474836.47 Nm
|
Only for "Referencing to positive stop"
(homing modes CwTorqueLimit [-2] and CcwTorqueLimit [-1]). The home position is set if the axis is stationary during the locking time and the actual torque is greater than the torque limit.
|
|
|
0x500A:079
|
TA axis parameter: Homing: Blocking time
0.000 ... [1.000] ... 2147483.647 s
|
||
|
0x500A:080
|
TA axis parameter: Homing: Touch probe configuration
|
||
|
1
|
TP1 - positive edge
|
||
|
2
|
TP1 - negative edge
|
||
|
0x500A:084
|
TA axis parameter: Home position
-214748.3648 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:090
|
TA axis parameter: Default control mode
–
Setting can only be changed if the inverter is disabled.
|
||
|
0
|
Position control via motor encoder
|
||
|
1
|
Position control via load encoder
|
||
|
10
|
Speed control via motor encoder
|
||
|
0x500A:104
|
TA axis parameter: Response to hardware limit switch error
|
||
|
12
|
Warning
|
||
|
23
|
Fault > inverter disabled
|
||
|
0x500A:105
|
TA axis parameter: Response to software position limit error
|
||
|
12
|
Warning
|
||
|
23
|
Fault > inverter disabled
|
||
|
0x500A:106
|
TA axis parameter: Response to error "max. values exceeded"
|
||
|
0
|
No response
|
||
|
12
|
Warning
|
||
|
23
|
Fault
|
||
|
0x500A:130
|
TA axis parameter: Position window size
0.0000 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:131
|
TA axis parameter: Position window dwell time
0.000 ... [0.000] ... 2147483.647 s
|
||
|
0x500A:135
|
TA axis parameter: Modulo positioning tolerance window
0.0000 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:136
|
TA axis parameter: Tolerance window actual position=set position upper limit
0.0000 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:137
|
TA axis parameter: Tolerance window actual position=set position lower limit
0.0000 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x500A:181
|
TA axis parameter: Manual jog velocity
0.0000 ... [360.0000] ... 214748.3647 unit/s
|
Profile parameters for the "Manual operation" function.
|
|
|
0x500A:182
|
TA axis parameter: Manual jog acceleration
0.00 ... [720.00] ... 21474836.47 unit/s²
|
||
|
0x500A:183
|
TA axis parameter: Manual jog deceleration
0.00 ... [720.00] ... 21474836.47 unit/s²
|
||
|
0x500A:184
|
TA axis parameter: Manual jog jerk
0.00 ... [7200.00] ... 21474836.47 unit/s³
|
||
|
0x500A:186
|
TA axis parameter: Deceleration of Halt
0.01 ... [720.00] ... 21474836.47 unit/s²
|
Profile parameters for the "Stop" function.
|
|
|
0x500A:187
|
TA axis parameter: Jerk of Halt
0.00 ... [7200.00] ... 21474836.47 unit/s³
|
||
|
0x500B:033
|
Load encoder: Gearbox factor - nominator
1 ... [1] ... 4294967295
–
Setting can only be changed if the inverter is disabled.
|
||
|
0x500B:034
|
Load encoder: Gearbox factor - denominator
1 ... [1] ... 4294967295
–
Setting can only be changed if the inverter is disabled.
|
||
|
0x500B:035
|
Load encoder: Load encoder mounting direction
–
Setting can only be changed if the inverter is disabled.
|
||
|
0
|
CW
|
||
|
1
|
CCW
|
||
|
0x500B:085
|
Load encoder: Homepos available for absolute encoder
|
||
|
0
|
Default behaviour
|
||
|
1
|
Permanently set
|
||
|
0x500B:086
|
Load encoder: Homing: Offset Position (for Mode 98 or Sub 85)
-214748.3648 ... [0.0000] ... 214748.3647 Unit
|
||
|
0x5020:011
|
Interface selection: TP1 source
|
||
|
11
|
Digital input 2, positive edge
|
||
|
12
|
Digital input 2, negative edge
|
||
Severity