Interface

Parameter
Address
Name / setting range / [default setting]
Information
0x2631:059
Function list: Source of negative hardware limit switch
–
Further possible settings: Trigger list 
 
Assignment of the source to which the negative hardware limit switch is connected, for example a digital input.
The monitoring of the travel range limits is designed to be fail-safe:
Trigger = FALSE: Negative hardware limit switch has been triggered.
Trigger = TRUE: Negative hardware limit switch in idle state.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:060
Function list: Source of positive hardware limit switch
–
Further possible settings: Trigger list 
 
Assignment of the source to which the positive hardware limit switch is connected, for example a digital input.
The monitoring of the travel range limits is designed to be fail-safe:
Trigger = FALSE: Positive hardware limit switch has been triggered.
Trigger = TRUE: Positive hardware limit switch in idle state.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:061
Function list: Source of flying homing
–
Further possible settings: Trigger list 
 
Assignment of the source to which the switch/measurement probe for the "On-the-fly referencing" function is connected, for example a digital input.
Trigger = TRUE: Switch/measurement button for "On-the-fly referencing" function has been triggered.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:062
Function list: Source of homing switch
–
Further possible settings: Trigger list 
 
Assignment of the source to which the reference switch is connected, for example a digital input.
Trigger = TRUE: Reference switch has been triggered.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:063
Function list: Manual jog positive
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Manual jog positive".
Trigger = TRUE: Manual operation in positive direction.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:064
Function list: Manual jog negative
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Manual jog negative".
Trigger = TRUE: Manual mode in negative direction.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:065
Function list: Halt
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Halt".
Trigger = TRUE: Trigger stop in the application.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:066
Function list: Start homing
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Start homing".
Trigger = TRUE: Start homing
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:067
Function list: Reset home position
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Reset home position".
Trigger = TRUE: Reset home position.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:068
Function list: Abort
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Abort".
Trigger = TRUE: Cancel active movement.
–
The drive is brought to a standstill via the active profile deceleration.
 
–
The drive switches to the "STOP" state.
 
Note: The delay to standstill is canceled when a new movement is ordered.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:069
Function list: Activate velocity overrride
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Activate velocity overrride".
Trigger = TRUE: Activate speed override.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:070
Function list: Profile number (bit 0)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for bit-coded selection of the travel profile.
Trigger = FALSE: Bit with valency 20 = 0
Trigger = TRUE: Bit with valency 20 = 1
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:071
Function list: Profile number (bit 1)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for bit-coded selection of the travel profile.
Trigger = FALSE: Bit with valency 21 = 0
Trigger = TRUE: Bit with valency 21 = 1
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:072
Function list: Profile number (bit 2)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for bit-coded selection of the travel profile.
Trigger = FALSE: Bit with valency 22 = 0
Trigger = TRUE: Bit with valency 22 = 1
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:073
Function list: Profile number (bit 3)
–
Further possible settings: Trigger list 
 
Assignment of a trigger for bit-coded selection of the travel profile.
Trigger = FALSE: Bit with valency 23 = 0
Trigger = TRUE: Bit with valency 23 = 1
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:074
Function list: Start
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Start".
Trigger = TRUE: Start positioning.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:075
Function list: Resume
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Resume".
Trigger = TRUE: Continue interrupted positioning.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:076
Function list: Deactivate touch probe
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Deactivate touch probe".
Trigger = TRUE: Deactivate touch probe.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2631:077
Function list: Activate external set position
–
Further possible settings: Trigger list 
 
Assignment of a trigger to the "Activate external set position".
Trigger = TRUE: Use the value set for the external setpoint position as the target position.
Trigger = FALSE: No action.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x5030:001
Table Positioning: Simulation of control signals
0 ... [0] ... 255
Bit 0
Enable control signal simulation
Bit = 1: The simulation of the control signals is activated.
Bit = 0: The control signals are transmitted via the active network interface.
Bit 1
Activate simulation of control word 1
Bit = 1: The simulation of control word 1 is activated.
Bit = 0: The control word is transmitted via the active network interface.
Bit 2
Activate simulation of control word 2
Bit = 1: The simulation of control word 2 is activated.
Bit = 0: The control word is transmitted via the active network interface.
Bit 3
Activate simulation of control word 3
Bit = 1: The simulation of control word 3 is activated.
Bit = 0: The control word is transmitted via the active network interface.
Bit 4
Activate simulation of control word 4
Bit = 1: The simulation of control word 4 is activated.
Bit = 0: The control word is transmitted via the active network interface.
Bit 5
Activate simulation of control word 5
Bit = 1: The simulation of control word 5 is activated.
Bit = 0: The control word is transmitted via the active network interface.
Bit 6
Activate simulation of control word 6
Bit = 1: The simulation of control word 6 is activated.
Bit = 0: The control word is transmitted via the active network interface.
Bit 7
Activate simulation of control word 7
Bit = 1: The simulation of control word 7 is activated.
Bit = 0: The control word is transmitted via the active network interface.
0x5030:008
Table Positioning: Activate flying homing
The "On-the-fly referencing" function can be used to set the home position of a mechanism while it is moving. There is no jerk and no compensating movement.
0
FALSE
The function is deactivated.
1
TRUE
The function is activated.
124
Control bit 24
The function is activated via the corresponding control bit of 0x5030:010.
125
Control bit 25
126
Control bit 26
127
Control bit 27
0x5030:009
Table Positioning: Activate "Stop positioning"
When positioning to a positive stop, the following error is permanently ignored during positioning. In this way, positioning against an obstacle can be carried out, for example to press materials with defined forces.
For positioning on a positive stop, the torque limits must be set according to the forces required for pressing.
0
FALSE
The function is deactivated.
1
TRUE
The function is activated.
124
Control bit 24
The function is activated via the corresponding control bit of 0x5030:010.
125
Control bit 25
126
Control bit 26
127
Control bit 27
0x5030:010
Table Positioning: Control signals
0 ... [0] ... 4294967295
Bit-coded control word for table positioning.
Bit 3
Enable operation
Bit = 1: The axis is enabled.
Bit = 1
↘
0: The rotating axis is stopped via the quick stop ramp and locked when at a standstill.
Bit 5
Jog positive
Bit = 1: The axis moves in the positive direction in manual mode. The axis stops when the positive software limit position is reached.
Bit 6
Jog negative
Bit = 1: The axis moves in the negative direction in manual mode. The axis stops when the negative software limit position is reached.
Bit 7
Fault reset
Bit = 1: Errors are reset when the causes are eliminated.
Bit 8
Halt
Bit = 1: A stop is triggered in the application.
Bit 9
Start homing
Bit = 1: Homing is started.
Bit 10
Reset home position
Bit = 1: The status information "Home position known" is reset.
Bit 11
Abort
Bit = 1: The active movement is canceled.
–
The axis is guided to standstill via the active profile deceleration.
 
–
The axis changes to "STOP".
 
Note: The delay to standstill is canceled when a new movement is ordered.
Bit 13
Activate velocity override
Bit = 1: The external speed override is activated.
Bit 14
Open brake manually
Bit = 1: The holding brake is opened.
Bit 16
Profile number (bit 1)
Bit with valency 20 for selecting the travel profile.
Bit 17
Profile number (bit 1)
Bit with valency 21 for selecting the travel profile.
Bit 18
Profile number (bit 2)
Bit with valency 22 for selecting the travel profile.
Bit 19
Profile number (bit 3)
Bit with valency 23 for selecting the travel profile.
Bit 20
Start positioning
Bit = 1: Positioning is started.
Bit 22
Resume positioning
Bit = 1: Interrupted positioning is continued.
Bit 23
Disable touch probe
Bit = 1: The touch probe function is deactivated.
Bit 24
Control bit 24
These control bits can be assigned to other table positioning functions.
Bit 25
Control bit 25
Bit 26
Control bit 26
Bit 27
Control bit 27
Bit 28
Activate external position
Bit = 1: The value set for the external setpoint position is used as the target position.
0x5030:011
Table Positioning: External velocity override
0.00 ... [0.00] ... 100.00 %
Value for external speed override.
0x5030:012
Table Positioning: External velocity
-214748.3648 ... [0.0000] ... 214748.3647 unit/s
External profile parameters
0x5030:014
Table Positioning: External acceleration
0.00 ... [0.00] ... 21474836.47 unit/s²
0x5030:015
Table Positioning: External deceleration
0.00 ... [0.00] ... 21474836.47 unit/s²
0x5030:016
Table Positioning: External jerk
0.00 ... [0.00] ... 42949672.95 unit/s³
0x5030:023
Table Positioning: External set position
-214748.3648 ... [0.0000] ... 214748.3647 Unit
0x5030:101
Table Positioning: Simulation of status signals
0x00 ... [0x00] ... 0x01
Bit 0
Enable control signal simulation
Bit = 1: The simulation of the status signals is activated.
Bit = 0: The status signals for table positioning are transmitted via the active network interface.
0x5030:110
Table Positioning: Status signals
0 ... [0] ... 4294967295
Bit-coded status word of the table positioning.
Bit 0
Ready for operation
Bit = 1: The axis is ready for switch-on.
Bit 1
Homing active
Bit = 1: Homing is active.
Bit 2
Operation enabled
Bit = 1: The axis is enabled.
Bit 3
Fault
Bit = 1: An error is active.
Bit 4
Homing done
Bit = 1: Homing was successfully completed, the home position was recognized.
Bit 5
Quick stop active
Bit = 1: Quick stop was triggered.
Bit 6
Jog active
Bit = 1: Manual mode is active.
Bit 7
Warning
Bit = 1: A warning is active.
Bit 8
Halt active
Bit = 1: A stop was triggered in the application.
Bit 9
Motor control in limitation
Bit = 1: The motor control is in limitation.
Bit 10
Set position reached
Bit = 1: Actual position = setpoint position
Bit 11
Abort busy
Bit = 1: The active movement is canceled.
Bit 12
Standstill
Bit = 1: The axis is at a standstill.
Bit 13
Direction of rotation inverted
Bit = 1: The rotating direction is inverted.
Bit 14
Holding brake released
Bit = 1: The holding brake is open.
Bit 15
STO active
Bit = 1: The "Safe Torque Off (STO)" safety function has safely switched off the axis.
Bit 16
Active profile (bit 0)
Bit with valency 20 for displaying the active positioning profile.
Bit 17
Active profile (bit 1)
Bit with valency 21 for displaying the active positioning profile.
Bit 18
Active profile (bit 2)
Bit with valency 22 for displaying the active positioning profile.
Bit 19
Active profile (bit 3)
Bit with valency 23 for displaying the active positioning profile.
Bit 20
Positioning profile active
Bit = 1: Positioning is active.
Bit 21
Positioning profile done
Bit = 1: Positioning has been completed.
Bit 22
Negative hardware limit switch active
Bit = 1: The negative hardware limit switch has been triggered.
Bit 23
Positive hardware limit switch active
Bit = 1: The positive hardware limit switch has been triggered.
Bit 24
Touch probe detected
Bit = 1: Touch probe was recognized.
Bit 25
Status bit 25
Bit without function
Bit 26
Status bit 26
Bit 27
Torque setpoint limited
Bit = 1: The setpoint torque is in limitation.
Bit 28
External position active
Bit = 1: The value set for the external setpoint position is used as the target position.
Bit 29
External velocity active
Bit = 1: The value set for the external speed is used.
Bit 30
External acceleration/deceleration/jerk active
Bit = 1: The values set for external acceleration, deceleration and jerk are used.
Bit 31
External torque limit active
Bit = 1: The values set for the external torque limits are used.