Analog output 1
With the "AO1" function assignment for connector X3.4, the drive provides an analog output.
Preconditions
–
The function assignment of connector X3.4 must be configured accordingly.
Configure function assignment
Configure function assignment –
The "AO1" function is available only on inverters with Extended-I/O.
Details
The analog output 1 is controlled with the signal selected in 0x2639:002.
The following settings are possible for the analog output:
–
Definition of the signal range ①
–
Definition of the output range ②
Diagnostic parameters:
–
The current output voltage is displayed in 0x2DAA:001.
–
The actual output current is displayed in 0x2DAA:002.
Definition of the signal range
The signal range results from the resolution of the selected signal multiplied by the set min and max signal value. Signals outside the signal range are cut off. For examples, see the following table:
|
Signal
|
Resolution
|
Min. signal
|
Max. signal
|
Signal range
|
|
Output frequency
|
0.1 Hz
|
0
|
1000
|
0 ... 100.0 Hz
|
|
Frequency setpoint
|
0.1 Hz
|
0
|
1000
|
0 ... 100.0 Hz
|
|
Analog input 1
|
0.1 %
|
0
|
1000
|
0 ... 100.0 %
|
|
Analog input 2
|
0.1 %
|
0
|
1000
|
0 ... 100.0 %
|
|
Motor current
|
0.1 A
|
0
|
100
|
0 ... 10.0 A
|
|
Output power
|
0.001 kW
|
0
|
250
|
0 ... 0.250 kW
|
|
Actual torque
|
0.1 % *
|
0
|
1000
|
0 ... 100.0 % *
|
|
NetWordIN3
|
0.1 %
|
200
|
500
|
20.0 ... 50.0 %
|
|
NetWordIN4
|
0.1 %
|
0
|
250
|
0 ... 25.0 %
|
|
* 100 % = Rated motor torque 0x6076
|
||||
Definition of the output range
The analog output can be configured as voltage source or current source. The output range selected in 0x2639:001 then corresponds to the configured signal range.
Configuration examples
Detailed configuration examples can be found in the following subchapters:
Parameter
Example: mirrored output range