Interface

The "EASY Starter" engineering tool (from version 1.28) supports the configuration of data mapping in a simple manner.
Settings
à
PLC configuration
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x24F0:000
Logic PLC RPDO mapping: Highest subindex
0 ... [0] ... 16
–
Setting can only be changed if the inverter is disabled.
 
0x24F0:001
Logic PLC RPDO mapping: Entry 1
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:002
Logic PLC RPDO mapping: Entry 2
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:003
Logic PLC RPDO mapping: Entry 3
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:004
Logic PLC RPDO mapping: Entry 4
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:005
Logic PLC RPDO mapping: Entry 5
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:006
Logic PLC RPDO mapping: Entry 6
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:007
Logic PLC RPDO mapping: Entry 7
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:008
Logic PLC RPDO mapping: Entry 8
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:009
Logic PLC RPDO mapping: Entry 9
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:010
Logic PLC RPDO mapping: Entry 10
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:011
Logic PLC RPDO mapping: Entry 11
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:012
Logic PLC RPDO mapping: Entry 12
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:013
Logic PLC RPDO mapping: Entry 13
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:014
Logic PLC RPDO mapping: Entry 14
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:015
Logic PLC RPDO mapping: Entry 15
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F0:016
Logic PLC RPDO mapping: Entry 16
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:000
Logic PLC TPDO mapping: Highest subindex
0 ... [0] ... 16
–
Setting can only be changed if the inverter is disabled.
 
0x24F1:001
Logic PLC TPDO mapping: Entry 1
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:002
Logic PLC TPDO mapping: Entry 2
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:003
Logic PLC TPDO mapping: Entry 3
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:004
Logic PLC TPDO mapping: Entry 4
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:005
Logic PLC TPDO mapping: Entry 5
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:006
Logic PLC TPDO mapping: Entry 6
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:007
Logic PLC TPDO mapping: Entry 7
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:008
Logic PLC TPDO mapping: Entry 8
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:009
Logic PLC TPDO mapping: Entry 9
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:010
Logic PLC TPDO mapping: Entry 10
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:011
Logic PLC TPDO mapping: Entry 11
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:012
Logic PLC TPDO mapping: Entry 12
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:013
Logic PLC TPDO mapping: Entry 13
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:014
Logic PLC TPDO mapping: Entry 14
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:015
Logic PLC TPDO mapping: Entry 15
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x24F1:016
Logic PLC TPDO mapping: Entry 16
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
0x2634:030
Digital outputs function: Logic PLC In bit 0
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 0 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:031
Digital outputs function: Logic PLC In bit 1
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 1 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:032
Digital outputs function: Logic PLC In bit 2
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 2 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:033
Digital outputs function: Logic PLC In bit 3
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 3 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:034
Digital outputs function: Logic PLC In bit 4
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 4 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:035
Digital outputs function: Logic PLC In bit 5
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 5 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:036
Digital outputs function: Logic PLC In bit 6
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 6 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:037
Digital outputs function: Logic PLC In bit 7
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 7 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:038
Digital outputs function: Logic PLC In bit 8
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 8 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:039
Digital outputs function: Logic PLC In bit 9
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 9 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:040
Digital outputs function: Logic PLC In bit 10
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 10 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:041
Digital outputs function: Logic PLC In bit 11
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 11 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:042
Digital outputs function: Logic PLC In bit 12
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 12 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:043
Digital outputs function: Logic PLC In bit 13
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 13 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:044
Digital outputs function: Logic PLC In bit 14
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 14 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2634:045
Digital outputs function: Logic PLC In bit 15
–
For further possible settings, see parameter 0x2634:010.
 
Assignment of a trigger to input bit 15 of the Logic PLC.
Trigger = FALSE: Bit is set to 0.
Trigger = TRUE: Bit is set to 1.
0
Not connected
No trigger assigned (trigger is constantly FALSE).
0x2661:004
Logic PLC inputs: Value 1 selection
Selection of the signal to be transferred to the Logic PLC as "Value 1".
0
Not active
No signal assigned.
1
Output frequency
Actual output frequency (resolution: 0.1 Hz).
2
Frequency setpoint
Current frequency setpoint (resolution: 0.1 Hz).
3
Analog input 1
Input signal of analog input 1 (resolution: 0.1 %).
4
Analog input 2
Input signal of analog input 2 (resolution: 0.1 %).
5
Motor current
Actual motor current (resolution: 0.1 A).
6
Output power
Actual output power (resolution: 0.001 kW).
7
Torque actual value
Current torque (resolution: 0.1 %).
–
100 % = permissible maximum torque 0x6072
 
8
Actual motor frequency
Actual motor output frequency (resolution: 0.1 Hz).
11
DC-bus voltage
Current DC-bus voltage (resolution: 1 V).
12
Device utilisation (ixt)
Current device utilization (resolution: 1 %).
20
NetWordIN3
Actual value of the NetWordIN3 data word (resolution: 0.1 %).
21
NetWordIN4
Actual value of the NetWordIN4 data word (resolution: 0.1 %).
210
IOL1 AI1 scaled value
Value is specified as process data object via IO-Link.
–
The function assignment of the connectors must be configured accordingly.
 
–
The IO-Link ports are only available on the inverter with Application-I/O.
 
211
IOL1 AI2 scaled value
212
IOL2 AI1 scaled value
213
IOL2 AI2 scaled value
214
IOL3 AI1 scaled value
215
IOL3 AI2 scaled value
216
IOL4 AI1 scaled value
217
IOL4 AI2 scaled value
230
Scaling1 value
Output values of the "Analog signal scaling" function. This function is used to scale internal analog signals (analog parameter values) for use within the inverter.
231
Scaling2 value
0x2661:005
Logic PLC inputs: Value 2 selection
–
For further possible settings, see parameter 0x2661:004.
 
Selection of the signal to be transferred to the Logic PLC as "Value 2".
0
Not active
No signal assigned.
0x2662:001
Logic PLC outputs: Output word
0 ... [0] ... 65535
Display of the status of the output bits from the Logic PLC.
–
The 16 output bits can also be selected as triggers for certain inverter functions.
 
Bit 0
Mapping bit 0
Bit 1
Mapping bit 1
Bit 2
Mapping bit 2
Bit 3
Mapping bit 3
Bit 4
Mapping bit 4
Bit 5
Mapping bit 5
Bit 6
Mapping bit 6
Bit 7
Mapping bit 7
Bit 8
Mapping bit 8
Bit 9
Mapping bit 9
Bit 10
Mapping bit 10
Bit 11
Mapping bit 11
Bit 12
Mapping bit 12
Bit 13
Mapping bit 13
Bit 14
Mapping bit 14
Bit 15
Mapping bit 15
0x2662:002
Logic PLC outputs: Value 1
0 ... [0] ... 65535
Display of the output value "Value 1" from the Logic PLC.
0x2662:003
Logic PLC outputs: Value 2
0 ... [0] ... 65535
Display of the output value "Value 2" from the Logic PLC.
0x2667:001
User parameter 16 bit: Entry 1
0 ... [0] ... 65535
Bit 0
Mapping bit 0
Bit 1
Mapping bit 1
Bit 2
Mapping bit 2
Bit 3
Mapping bit 3
Bit 4
Mapping bit 4
Bit 5
Mapping bit 5
Bit 6
Mapping bit 6
Bit 7
Mapping bit 7
Bit 8
Mapping bit 8
Bit 9
Mapping bit 9
Bit 10
Mapping bit 10
Bit 11
Mapping bit 11
Bit 12
Mapping bit 12
Bit 13
Mapping bit 13
Bit 14
Mapping bit 14
Bit 15
Mapping bit 15
0x2667:002
User parameter 16 bit: Entry 2
0 ... [0] ... 65535
0x2667:003
User parameter 16 bit: Entry 3
0 ... [0] ... 65535
0x2667:004
User parameter 16 bit: Entry 4
0 ... [0] ... 65535
0x2667:005
User parameter 16 bit: Entry 5
0 ... [0] ... 65535
0x5811:001
Configuration PLC application: Output data at stopped Logic PLC
–
Setting can only be changed if the inverter is disabled.
 
0
Keep last data
1
Clear data
0x5811:002
Configuration PLC application: Error response on exception
Associated event ID:
–
24704 | 0x6080 - Logic PLC exception error
 
0
No response
11
Information
12
Warning
16
Trouble
23
Fault > inverter disabled