Status LEDs
|
Function included in variant:
|
|
|
Extended Safety
|
The LEDs "RDY" and "ERR" show the current safety status:
Fig. 1: Position of the RDY and ERR LEDs
DANGER!Unreliable status information possible due to LEDs.
LEDs are not reliable status indicators. There is no guarantee that the LEDs provide accurate information.
Possible consequences: Death or severe injuries
▶
Only use LEDs for general diagnostics during commissioning or troubleshooting.
▶
Do not use LEDs as status displays.
|
LED "RDY" (yellow)
|
|
Status
|
Meaning
|
|
off
|
|
-
|
No status message active.
|
|
blinking (2 Hz)
|
Service status
|
Transfer of parameter set requested.
|
|
LED "RDY" (yellow)
|
LED "ERR" (red)
|
Status
|
Meaning
|
|
on
|
off
|
Restart acknowledgment requested
|
The device is working correctly.
|
|
flashes (2 Hz)
|
During startup, a modified parameter set was detected in the "Init" state.
|
||
|
flashes (4 Hz)
|
During startup, a changed safety address was detected in the "Init" state.
|
||
|
The detection of a firmware update is indicated by the subsequent flashing of the safety LEDs.
|
|||
|
on
|
1 second, increasing
|
Software confirmation requested
|
During startup, a modified safety-related software component (-or- was detected.
|
|
LED "RDY" (yellow)
|
LED "ERR" (red)
|
Status
|
Meaning
|
|
|
off
|
-
|
The device is working correctly.
|
|
|
blinking (2 Hz)
|
Error
|
One of the following errors has been detected:
–
A monitoring device has been activated.
–
An acknowledgeable error is active.
–
Discrepancy of the inputs
|
|
blinking (2 Hz)
|
blinking (2 Hz)
|
One of the following errors has been detected:
–
Discrepancy of the configuration parameters
–
CRC checksum error
|
|
|
|
blinking (4 Hz)
|
Safety bus error
|
Communication via the safety bus is not established:
–
There is no valid configuration.
–
The start-up has not been completed yet.
|
|
LED "RDY" (yellow)
|
LED "ERR" (red)
|
Status
|
Meaning
|
|
blinking
|
blinking
|
Critical system error
|
–
"Lock-out" (CPU stopped)
–
STO is active.
–
If the system error occurs again after switching the 24 V supply, the device is defective. It must be replaced.
|