Status LEDs

Function included in variant:
Extended Safety
 
The LEDs "RDY" and "ERR" show the current safety status:
 
Fig. 1: Position of the RDY and ERR LEDs
 
DANGER!
Unreliable status information possible due to LEDs.
LEDs are not reliable status indicators. There is no guarantee that the LEDs provide accurate information.
Possible consequences: Death or severe injuries
▶
Only use LEDs for general diagnostics during commissioning or troubleshooting.
 
▶
Do not use LEDs as status displays.
 
 
 
LED "RDY" (yellow)
Status
Meaning
off
-
No status message active.
blinking (2 Hz)
Service status
Transfer of parameter set requested.
 
Display for requested acknowledgment
LED "RDY" (yellow)
LED "ERR" (red)
Status
Meaning
on
off
Restart acknowledgment requested
The device is working correctly.
flashes (2 Hz)
During startup, a modified parameter set was detected in the "Init" state.
flashes (4 Hz)
During startup, a changed safety address was detected in the "Init" state.
The detection of a firmware update is indicated by the subsequent flashing of the safety LEDs.
on
1 second, increasing
Software confirmation requested
During startup, a modified safety-related software component (-or- was detected.
 
Display in the event of errors
LED "RDY" (yellow)
LED "ERR" (red)
Status
Meaning
off
-
The device is working correctly.
blinking (2 Hz)
Error
One of the following errors has been detected:
–
A monitoring device has been activated.
 
–
An acknowledgeable error is active.
 
–
Discrepancy of the inputs
 
blinking (2 Hz)
blinking (2 Hz)
One of the following errors has been detected:
–
Discrepancy of the configuration parameters
 
–
CRC checksum error
 
blinking (4 Hz)
Safety bus error
Communication via the safety bus is not established:
–
There is no valid configuration.
 
–
The start-up has not been completed yet.
 
 
Display for critical device errors
LED "RDY" (yellow)
LED "ERR" (red)
Status
Meaning
blinking
blinking
Critical system error
–
"Lock-out" (CPU stopped)
 
–
STO is active.
 
–
If the system error occurs again after switching the 24 V supply, the device is defective. It must be replaced.