Device exchange

Exchange a maximum of one safe device before recommissioning.
 
The following procedure assumes that the safe parameter set for the application is available as a file. Otherwise, a complete commissioning of the functional safety must be carried out.
 
How to replace a safe device with Extended Safety:
Preconditions:
✓
The safe parameter set for the application is available as a file.
 
✓
There is an online connection between the engineering tool and the replacement device.
 
1.
Check the compatibility of the replacement device.
 
2.
Open the parameterization dialog for safety parameters:
 
a.
»EASY Starter«: Open the Safety parameter list tab.
 
b.
»PLC Designer«: In the device tree, under the axis, open the object Safety parameter set in the device tree under the axis.
 
3.
Reset the safe parameter set to the default settings if the replacement device was previously used for test purposes or for another application:
 
a.
Execute the "Reset safe parameter set in the device" command.
 
b.
Enter password (default setting: "Lenze Safety").
 
c.
Confirm the query as to whether the safe parameter set in the device should be reset with "Yes".
 
4.
Load the safe parameter set for the application from the file into the replacement device:
 
a.
Execute the "Load safety parameter set from file" command.
 
b.
Enter password (default setting: "Lenze Safety").
 
c.
Confirm the query as to whether the existing safe parameter set should be overwritten with the parameter set from the file with "Yes".
 
5.
Transfer the safe parameter set to the replacement device.
 
6.
Carry out a functional test.