CANopen

CANopen® is an internationally approved communication protocol which is designed for commercial and industrial automation applications.
 
–
CANopen® is a registered community trademark of the CAN in Automation e. V user organisation.
 
–
Detailed information on CANopen can be found on the web page of the CAN in Automation (CiA) user organisation: www.can-cia.org
 
–
Information about the dimensioning of a CANopen network can be found in the configuration document for the inverter.
 
 
Preconditions
–
The inverter is equipped with the "CANopen" network option.
 
–
The network is terminated by one bus terminating resistor each at the first and last physical node. See "Typical topologies”.
 
–
The DIP switches for node address, baud rate and bus terminating resistor are correctly set, see: Basic setting and options 
 
–
The required EDS device description files for the inverters to be put into operation are loaded in the master (PLC).
 
 
 
Device description files for Lenze products can be found on the Internet:
www.Lenze.com 
à
Downloads
à
Product-related Application Knowledge Base articles
 
 
Details
–
The implementation of the CANopen communication profile
(CiA DS301, version 4.02) enables baud rates of 20 kbps to 1 Mbps.
 
–
For establishing a simple network connection, the inverter provides predefined control and status words for these profiles.
CiA 402 device profile 
AC drive 
Lenze LECOM profile 
There are also additional mappable data words to individually control the inverter:
 
–
The inverter control is preconfigured via a CiA control word.
 
 
Typical topology
Line