SLVC controller

For a quick commissioning, the calculations and settings are made automatically during the motor calibration.
 
Preconditions
The SLVC controller is only effective in the motor control type "Sensorless vector control (SLVC)".
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B40:001
Gain
0.0000 ... [0.2686]* ... 1000.0000 Hz/A
* Default setting dependent on the model.
Gain of the SLVC-Q controller.
0x2B40:002
Reset time
1.0 ... [2.3]* ... 2000.0 ms
* Default setting dependent on the model.
Reset time of the SLVC-Q controller.