General settings

This chapter provides information on general settings of feedback systems for the motor control.
 
Pressing the Select resolver or Select encoder button displays a list of resolvers or encoders.
If the displayed list contains the feedback system used, the data is applied automatically.
Otherwise, you must enter the data of the feedback system manually.
 
Monitoring of the encoder cable for wire breakage
The resolver or encoder cable can be monitored for wire breakage in the default settings of parameter 0x2C45.
DANGER!
When the encoder / resolver is used as a motor encoder, safe motor operation is not possible in the event of an error.
Destruction of system parts
▶
Fault should always be used as a response for resolver/encoder wire breakage monitoring.
 
▶
To prevent interference injections when using an encoder, only use shielded motor and encoder cables.
 
 
 
Wire breakage monitoring trips in the following cases:
–
Resolver
 
–
Wire breakage in the encoder cable
 
–
When the resolver impedance is too great
 
–
In the event of interference injections (EMC interference)
 
 
–
Encoder
 
–
Wire breakage in the encoder cable
 
 
 
Sensitivity of wire breakage monitoring
The sensitivity of wire breakage monitoring can be set as a percentage using the 0x2C47 parameter.
Reducing the monitoring sensitivity is advantageous in environments that are severely affected by EMC problems.
If the sensitivity is not reduced (100 %), the software response time of monitoring in case of an encoder is approx. 3.5 ms and in case of a resolver 0.3 ms.
Halving the sensitivity means doubling the response time.
 
NOTICE
A reduced sensitivity delays the response in case of wire breakage!
Destruction of system parts by reduced sensitivity of the open-circuit monitoring.
▶
Increase the sensitivity to reduce the monitoring response time.
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C45
Motor feedback error response
0
No response
1
Warning
2
Trouble
0x2C46
Number of the absolute ascertainable revolutions of motor encoder
–
Read only
 
Is set by the firmware according to the available version:
–
0: no absolute value encoder (sin/cos encoder) or resolver with number of pole pairs > 1
 
–
1: Single-turn absolute value encoder or resolver with number of pole pairs = 1
 
–
>1: Multi-turn absolute value encoder
 
0x2C47
Open circuit detection sensitivity of motor encoder
1 ... [100] ... 100 %
The sensitivity can be reduced by percentage, e. g. in case of EMC interferences.
0x608F:001
Position encoder resolution: Encoder increments
–
Setting can only be changed if the inverter is disabled.
 
Position encoder resolution: Encoder increments
Setting the number of bits to be used for resolving a mechanical motor revolution.
65536
16 bit
262144
18 bit
1048576
20 bit
4194304
22 bit
16777216
24 bit
67108864
26 bit
268435456
28 bit
1073741824
30 bit
0x608F:002
Position encoder resolution: Motor revolutions
1 ... [1] ... 1
–
Setting can only be changed if the inverter is disabled.
 
Denominator of the position resolution: Number of motor revolutions.
Only setting "1" is accepted.
0x6090:001
Velocity encoder resolution: Encoder increments/s
0 ... [33554432] ... 2147483647
–
Setting can only be changed if the inverter is disabled.
 
Setting of the encoder increments/s.
0x6090:002
Velocity encoder resolution: Motor revolutions/s
0 ... [125] ... 2147483647
–
Setting can only be changed if the inverter is disabled.
 
Setting of the motor revolutions/s.