Resolver settings

Resolvers with a number of pole pairs > 1 are not absolute value encoders.
Bit 4 in 0x2833 (Lenze status word 2) therefore remains set to "0".
The "distinguishable revolutions" specification in 0x2C46 is also set to "0".
 
 
The following applies to synchronous motors:
–
When the number of motor pole pairs to the number of resolver pole pairs is an integer ratio (0x2C01:001), the pole position only has to be identified once.
 
–
When the number of motor pole pairs to the number of resolver pole pairs is a non-integer ratio (0x2C01:001), the pole position must be identified every time the inverter is connected to 24 V.Synchronous motor: Pole position identification (PPI)
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2822:025
Axis commands: Get motor encoder characteristic (resolver)
Values determined in order to compensate for resolver faults.
0
Off/Ready
1
On/Start
2
In progress
3
Action cancelled
4
No access
5
No access (Device disabled)
0x2C43
Motor encoder resolver number of pole pairs
1 ... [1] ... 10
–
Setting can only be changed if the inverter is disabled.
 
Setting of the number of pole pairs.