Inverter diagnostics

The following parameters supply some information about the current operating status of the inverter.
 
This includes the following information:
–
Active access protection after log-in by means of PIN1/PIN2
 
–
Currently loaded parameter settings
 
–
Cause(s) for disable, quick stop and stop.
 
–
Active control source and active setpoint source
 
–
Active operating mode
 
–
Status of the internal motor control
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2010:001
Device event monitor: EreignisortEvent location
–
Read only
 
Display of the event location for the currently pending event.
0
No error
1
Functional safety
4
Basic settings
5
Communication
6
Kinematics
7
Motion
8
Technology application
0x2010:002
Device event monitor: Severity
–
Read only
 
Display of the severity level for the currently active event.
0
No response
1
Fault > CiA402
2
Warning
11
Information
13
Warning locked
15
Trouble > logbook only
16
Trouble
18
Fault > logbook only
19
Fault > Application quick stop > Quick stop
20
Fault > inverter quick stop > quick stop
21
Fault > inverter quick stop > inverter disabled
23
Fault > inverter disabled
0x2010:003
Device event monitor: Event status
–
Read only
 
Display of the event status for the currently pending event.
0
No event active
1
Reset possible
2
Reset not possible
0x2010:005
Device event monitor: Number of current event
–
Read only
 
Display of the event ID for the currently pending event.
0x2010:006
Device event monitor: Time stamp of current event
–
Read only: x ns
 
Display of the time stamp for the current upcoming event.
0x2040
Access protection status
–
Read only
 
Bit-coded display of the active access protection after login by PIN1/PIN2.
Bit  0
No write access
Bit  1
Only favorites changeable
0x2539:001
Hardware-Diagnose: External supply voltage
–
Read only: x.x V
 
0x2539:002
Hardware-Diagnose: Control board temperature
–
Read only: x.x °C
 
0x2823
Status of axis commands
–
Read only: x %
 
0x282A:001
Status words: Cause of disable
–
Read only
 
Bit-coded display of the cause(s) for disabled inverter.
Bit  2
Axis command
1 = the inverter was disabled via axis command 0x2822:001.
Bit  7
Drive not ready
1 = the inverter was disabled internally since the drive was not ready for operation.
Possible causes:
–
Under/overvoltage in the DC bus
 
–
Defective device hardware
 
Bit  12
CiA402 Inverter disabled
1 = the inverter was disabled by the internal state machine.
The bit is only set if
–
Operating mode 0x6060 = "CiA: Velocity mode (vl) [2]" and
 
–
state machine in the "Switch on disabled" state and
 
–
the state change has not been carried out via the "Disable operation" command.
 
Bit  14
Safety
Bit  16
PROFINET energy pause active
-
0x282A:004
Status words: Extended status word
–
Read only
 
Bit-coded status word.
Bit  0
Brake is opened
-
Bit  1
Reserved
Bit  2
Reserved
0x2831
Inverter status word
–
Read only
 
Bit coded status word of the internal motor control.
Bit  0
Position controller in limitation
-
Bit  1
Speed setpoint 1 limited
1 = input of speed controller 1 in limitation.
Bit  2
Speed controller in limitation
1 = output of speed controller 1 in limitation.
Bit  3
Torque setpoint limited
1 = setpoint torque in limitation.
Bit  4
Q-current setpoint limited
1 = setpoint current in limitation.
Bit  5
Speed setpoint 2 limited
1 = input of speed controller
2 in "torque mode" in limitation.
Bit  6
Upper speed limit active
1 = in "torque mode", the speed is limited to upper
speed limit 0x2946:001
.
Bit  7
Lower speed limit active
1 = in "torque mode", the speed is limited to lower
speed limit 0x2946:002
.
Bit  8
Flying restart active
-
Bit  9
Flying restart completed
Bit  10
Output frequency limited
1 = setpoint frequency with V/f operation in limitation.
Bit  11
Magnetization completed
1 = Magnetisation completed during V/f operation.
Otherwise 0.
Bit  12
Motor phase error
1 = motor phase failure detection active.
Bit  13
Feedback open circuit
-
Bit  14
Error reset blocking time active
1 = the error can only be reset when the blocking time has elapsed.
Bit  15
Clamp active
-
0x2833
Inverter status word 2
–
Read only
 
Bit-coded status word 2 of the inverter.
Bit  0
Motor encoder modified
Bit  1
Manual test mode active
1 = manual test mode active.
Bit  2
Manual control active
1 = manual control active.
Bit  4
Motor encoder = absolute value encoder
-
Bit  5
Motor encoder absolute position available
Bit  6
DC braking active
1 = DC braking
active.
Bit  7
Motor encoder angle drift invalid
-
Bit  8
Load encoder modified
Bit  9
Load encoder angle drift invalid
Bit  10
Load encoder = absolute value encoder
Bit  11
Load encoder absolute position available
Bit  12
Brake open
Bit  13
Cable check active
Bit  14
Mains failure detected
0x284F
Current error
–
Read only
 
Test display of the current error.
–
This object contains a reference for the text to be displayed from the ESI file as well as the substitution values for all wildcards in this text.
 
–
The text has the same structure as the diagnostic messages in the history buffer.
 
0x603F
Error code
–
Read only
 
Error message
0x6061
CiA: Active operation mode
–
Read only
 
CiA: Active operation mode
-13
MS: Manual jog open loop (MOL)
Manufacturer-specific manual control
-12
MS: Pole position identification (PPI)
Manufacturer-specific pole position identification (PLI)
-11
Identification
-10
Test mode
0
No selection
No selection
2
CiA: Velocity mode (vl)
8
CiA: Cyclic sync position (csp)
9
CiA: Cyclic sync velocity mode (csv)
10
CiA: Cyclic sync torque mode (cst)