Status LEDs
The "RDY" and "ERR" LED status displays on the front of the inverter
provide some quick information about certain operating states.
|
"RDY" LED (blue)
|
"ERR" LED (red)
|
Status/meaning
|
|
Off
|
Off
|
Supply voltage not available.
|
|
On
|
On
|
Initialisation in progress (inverter is being started.)
|
|
Blinks (1 Hz)
|
Off
|
Safe torque off (STO) active. The inverter has been inhibited by the integrated safety system.
|
|
Blinks (1 Hz)
|
On
|
Inverter inhibited, error active.
|
|
On
|
Off
|
Inverter enabled.
Motor rotates according to the specified setpoint or quick stop is active.
|
|
Both LEDs are blinking in a rapidly alternating mode
|
Firmware update active.
|
|
|
Both LEDs are blinking in a very rapidly synchronous mode
|
"Visual tracking" function is active.
|
|
The description of the network-specific "BUS RDY" and "BUS ERR" LEDs can be found in chapters
Safe torque off (STO)