Service life diagnostics

The following parameters provide some information about the use of the inverter.
 
This includes the following information:
–
Operating and power-on time of the inverter/control unit
 
–
Operating time of the internal fan
 
–
Number of switching cycles of the mains voltage
 
–
Number of switching cycles of the relay
 
–
Number of short-circuits and earth faults that have occurred
 
–
Display of the number of "Clamp responded too often" errors that have occurred.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D81:001
Life-diagnosis: Operating time
–
Read only: x s
 
Display showing for how long the device has been running so far (device status “operation enabled”).
0x2D81:002
Life-diagnosis: Power-on time
–
Read only: x s
 
Display showing for how long the device has been supplied with line voltage so far.
0x2D81:004
Life-diagnosis: Main switching cycles
–
Read only
 
Display of the number of switching cycles of the mains voltage.
0x2D81:006
Life-diagnosis: Short-circuit counter
–
Read only
 
Display of the number of short circuits that have occurred.
0x2D81:007
Life-diagnosis: Earth fault counter
–
Read only
 
Display of the number of earth faults that have occurred.
0x2D81:009
Life-diagnosis: Fan operating time
–
Read only: x s
 
Display showing for how long the internal fan has been running so far.