Heatsink temperature monitoring

In order to avoid an impermissible heating of the servo inverter, the temperature of the heatsink is detected and monitored.
The temperature of the heatsink is measured in the temperature range of 0 ... 80 °C with a tolerance of -2 ... +4 °C. Beyond this temperature range, the measuring accuracy decreases faster.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D84:001
Heatsink temperature: Heatsink temperature
–
Read only: x.x °C
 
Display of the current heatsink temperature.
0x2D84:002
Heatsink temperature: Warning threshold
50.0 ... [90.0] ... 100.0 °C
Warning threshold for temperature monitoring.
–
If the heatsink temperature exceeds the threshold set here, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of approx. 5 °C.
 
–
If the heatsink temperature increases further and exceeds the non-adjustable error threshold (100 °C), the inverter changes to the "Fault" device status. The inverter is disabled and thus any further operation is stopped.