Switching frequency changeover

The output voltage of the inverter is a DC voltage with sine-coded pulse width modulation (PWM). This corresponds by approximation to a AC voltage with variable frequency. The frequency of the PWM pulses is adjustable and is called "switching frequency".
 
Details
The switching frequency has an impact on the smooth running performance and the noise generation in the motor connected as well as on the power loss in the inverter. The lower the switching frequency, the better the concentricity factor, the smaller the power loss and the higher the noise generation.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2939
Switching frequency
Selection of the inverter switching frequency.
Abbreviations used:
–
"Variable": Adaptation of the switching frequency as afunction of the current. The carrier frequency is reduced depending on the heat sink temperature and the ixt load.
 
–
"Fixed": The carrier frequency is fixed, no frequency reduction.
 
–
"Drive-optimised": reduces the capacitive currents from the motor to the earth.
 
–
"Min. Pv": reduces the capacitive currents from the motor to the earth and optimizes power dissipation.
 
2
8 kHz variable / drive-optimised
3
16 kHz variable / drive-optimised
6
4 kHz fixed / drive-optimised
7
8 kHz fixed / drive-optimised
8
16 kHz fixed / drive-optimised