Motor control mode

The inverter supports different modes for closed-loop/open-loop motor control.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C00
Motor control mode
–
Setting can only be changed if the inverter is disabled.
 
Selection of the motor control mode.
1
Servoregelung (SC-PSM)
This control mode is used for servo control of a synchronous motor.
A motor encoder must be connected to the inverter. This motor encoder serves as a feedback system for engine control.
2
Servo control (SC ASM)
This control mode is used for servo control of an asynchronous motor.
A motor encoder must be connected to the inverter. This motor encoder is used as a feedback system for the motor control.
3
Sensorless control (SL PSM)
4
Sensorless vector control (SLVC)
This control type is used for sensorless vector control of an asynchronous motor.
6
V/f characteristic control (VFC open loop)
This control mode is used for the speed control of an asynchronous motor via a V/f characteristic and is the simplest control mode.
7
V/f characteristic control (VFC closed loop)
The control mode is used for speed control of an asynchronous motor via a V/f characteristic with speed feedback.
A motor encoder must be connected to the inverter. This motor encoder is used as a feedback system for the motor control.
 
The detailed description of each motor control type can be found in the chapter "Configuring the motor control".
 
Supplementary chapters:
–
Chapter "Configure feedback system for motor control" describes how to set resolvers or sine/cosine encoders as motor feedback.
 
–
Chapter "" describes how a higher-level control loop can be used as an actual value feedback application for higher accuracy.