Mains voltage

The rated mains voltage set for the inverter has an impact on the operating range of the inverter.
 
Setting-up operation
For setup, the inverter can be operated with 15 V ... 60 V DC voltage.
–
Setting: 0x2540:001 = [4] 60 V DC (setting-up operation).
 
–
Supply via DC terminal X101 (+UG/-UG).
 
 
Voltage thresholds for monitoring the DC-bus voltage
–
The warning thresholds for monitoring are adjustable.
 
–
The error thresholds and reset thresholds for monitoring result from the rated mains voltage set.
 
Rated mains voltage
Undervoltage thresholds
Overvoltage thresholds
Warning threshold
Error threshold
Reset threshold
Warning threshold
Error threshold
Reset threshold
Setting in
Setting in
Display in
Display in
Setting in 0x2540:005
Display in
Display in
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2540:001
Mains settings: Rated mains voltage
Selection of the mains voltage for actuating the inverter.
0
230 Veff
1
400 Veff
2
480 Veff
4
60 V DC (setting-up operation)
10
230 Veff/reduced LU level
11
400 Veff/reduced LU level
12
480 Veff/reduced LU level
0x2540:002
Mains settings: Undervoltage warning threshold
0 ... [430] ... 800 V
Monitoring for undervoltage (LU) in the DC bus: Setting of the warning threshold.
–
If the DC voltage in the DC bus falls below the threshold set, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of 10 V.
 
0x2540:003
Mains settings: Undervoltage error threshold
–
Read only: x V
 
Monitoring for undervoltage (LU) in the DC bus: Display of the fixed threshold.
–
If the DC voltage in the DC bus falls below the threshold displayed, the error"" response is triggered.
 
0x2540:004
Mains settings: Undervoltage reset threshold
–
Read only: x V
 
Display of the fixed reset threshold for monitoring DC bus undervoltage.
0x2540:005
Mains settings: Overvoltage warning threshold
0 ... [795] ... 800 V
Monitoring for overvoltage (OU) in the DC bus: Setting of the warning threshold.
–
If the DC bus voltage exceeds the threshold set, the inverter outputs a warning.
 
–
The warning is reset with a hysteresis of 10 V.
 
0x2540:006
Mains settings: Overvoltage error threshold
–
Read only: x V
 
Monitoring for overvoltage (OU) in the DC bus: Display of the fixed threshold.
–
If the DC-bus voltage exceeds the threshold displayed, the "Fault" response is triggered.
 
0x2540:007
Mains settings: Overvoltage reset threshold
–
Read only: x V
 
Display of the fixed reset threshold for monitoring DC bus overvoltage.
0x2540:008
Mains settings: DC link voltage critical
–
Read only
 
Display of value "1": the DC-bus voltage has reached a critical value.