Advanced Safety
FSoE output data
The safety controller transmits FSoE output data (control commands) to the inverter:
–
Data length: 11 bytes
–
Control commands are LOW-active, the bit state "0" activates the function.
–
Exceptions: See details in the table.
|
Byte-Offset
|
Bit-Offset
|
|||||||
|
Bit 7
|
Bit 6
|
Bit 5
|
Bit 4
|
Bit 3
|
Bit 2
|
Bit 1
|
Bit 0
|
|
|
Byte 0
|
Command (CMD)
|
|||||||
|
Byte 1
|
AIE
(0↗1)
|
-
|
-
|
-
|
-
|
-
|
SS1
|
STO
|
|
Byte 2
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
AIS
(0↗1)
|
|
Byte 3
|
CRC_0 (low-byte)
|
|||||||
|
Byte 4
|
CRC_0 (high-byte)
|
|||||||
|
Byte 5
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
|
Byte 6
|
-
|
-
|
-
|
-
|
-
|
SBC
|
-
|
|
|
Byte 7
|
CRC_1 (low-byte)
|
|||||||
|
Byte 8
|
CRC_1 (high-byte)
|
|||||||
|
Byte 9
|
Connection-ID (low-byte)
|
|||||||
|
Byte 10
|
Connection-ID (high-byte)
|
|||||||
FSoE input data
The inverter transmits FSoE input data (status information) to the safety controller:
–
Data length: 19 bytes
–
Status information is HIGH-active, the bit status "1" indicates the active status information.
|
Byte offset
|
Bit offset
|
|||||||
|
Bit 7
|
Bit 6
|
Bit 5
|
Bit 4
|
Bit 3
|
Bit 2
|
Bit 1
|
Bit 0
|
|
|
Byte 0
|
Command (CMD)
|
|||||||
|
Byte 1
|
Error active
|
-
|
-
|
-
|
-
|
-
|
-
|
STO active
|
|
Byte 2
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
SS1 active
|
|
Byte 3
|
CRC_0 (low-byte)
|
|||||||
|
Byte 4
|
CRC_0 (high-byte)
|
|||||||
|
Byte 5
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
|
Byte 6
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
|
Byte 7
|
CRC_1 (low-byte)
|
|||||||
|
Byte 8
|
CRC_1 (high-byte)
|
|||||||
|
Byte 9
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
|
Byte 10
|
-
|
-
|
-
|
-
|
MUT active
|
-
|
-
|
-
|
|
Byte 11
|
CRC_2 (low-byte)
|
|||||||
|
Byte 12
|
CRC_2 (high-byte)
|
|||||||
|
Byte 13
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
|
Byte 14
|
-
|
-
|
-
|
-
|
-
|
SBC activated
|
SBC active
|
-
|
|
Byte 15
|
CRC_3 (low-byte)
|
|||||||
|
Byte 16
|
CRC_3 (high-byte)
|
|||||||
|
Byte 17
|
Connection-ID (low-byte)
|
|||||||
|
Byte 18
|
Connection-ID (high-byte)
|
|||||||