Advanced Safety
FSoE output data
The safety controller transmits FSoE output data (control commands) to the inverter:
–
Data length: 11 bytes
 
–
Control commands are LOW-active, the bit state "0" activates the function.
 
–
Exceptions: See details in the table.
 
Byte-Offset
Bit-Offset
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
Command (CMD)
Byte 1
AIE
(0↗1)
-
-
-
-
-
SS1
STO
Byte 2
-
-
-
-
-
-
-
AIS
(0↗1)
Byte 3
CRC_0 (low-byte)
Byte 4
CRC_0 (high-byte)
Byte 5
-
-
-
-
-
-
-
-
Byte 6
-
-
-
-
-
SBC
-
Byte 7
CRC_1 (low-byte)
Byte 8
CRC_1 (high-byte)
Byte 9
Connection-ID (low-byte)
Byte 10
Connection-ID (high-byte)
 
FSoE input data
The inverter transmits FSoE input data (status information) to the safety controller:
–
Data length: 19 bytes
 
–
Status information is HIGH-active, the bit status "1" indicates the active status information.
 
Byte offset
Bit offset
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
Command (CMD)
Byte 1
Error active
-
-
-
-
-
-
STO active
Byte 2
-
-
-
-
-
-
-
SS1 active
Byte 3
CRC_0 (low-byte)
Byte 4
CRC_0 (high-byte)
Byte 5
-
-
-
-
-
-
-
-
Byte 6
-
-
-
-
-
-
-
-
Byte 7
CRC_1 (low-byte)
Byte 8
CRC_1 (high-byte)
Byte 9
-
-
-
-
-
-
-
-
Byte 10
-
-
-
-
MUT active
-
-
-
Byte 11
CRC_2 (low-byte)
Byte 12
CRC_2 (high-byte)
Byte 13
-
-
-
-
-
-
-
-
Byte 14
-
-
-
-
-
SBC activated
SBC active
-
Byte 15
CRC_3 (low-byte)
Byte 16
CRC_3 (high-byte)
Byte 17
Connection-ID (low-byte)
Byte 18
Connection-ID (high-byte)