Safe parameter setting

In »EASY Starter« and »PLC Designer«, safety parameters can only be set and transferred using the +safety parameter list+. When a device featuring integrated safety technology or a safety module is selected in the device list, the +safety parameter list+ becomes available in the form of an additional tab.
 
 
The safe parameterization is checked for plausibility.
The plausibility check rejects ambiguous or contradictory settings until they have been parameterized correctly. Only then can the parameters be saved.
 
 
Safe parameter setting
When using online communication via a bus system, several users can access the same drive simultaneously and process the safe parameter set. After transferring the safe parameters, check the checksums (CRC) in the safety parameter list dialog. The checksums of the project must correspond to the checksums of the safety option.
The consistency of the safe parameters must be ensured by organisational measures because there are no technical means to avoid multiple users accessing parameter sets at the same time.
 
 
Parameter setting
Safety-relevant parameters can only be transmitted to the safety option by safe parameter setting. The parameter set is saved on the SD card and and in the safety option with a unique safety address.
Safe parameter setting can only be performed in the service status. The service status means:
–
Stop is active and the drive is switched to torqueless operation (STO).
 
–
Communication via the safety bus is active but passivated.
 
The service status can be activated using the
»
Easy Starter
«
. Initializing the safety option serves to deactivate the service status.
The service status is activated when a deviation is detected in the safe parameter set on the safety option.
 
 
Parameter setting using the Easy Starter
From
»
Easy Starter
«
version 01.11 onwards, a safe parameter setting is supported. The functions of the Safety parameter list are documented in the online help.
 
Password
To save a safe parameter set, a password is required. The preset password is "Lenze Safety". The password can be changed and must have at least six characters.
The command Reset safe parameter set in the device serves to delete the safe parameter set. The safety functions must be re-parameterized after the reset. The password is reset to the preset password "Lenze Safety".
 
Acknowledge parameter set or safety address
 
 
Parameter sets and axes
The unambiguousness of an axis with safety functions in a drive system can be achieved by means of the safety address. When a safety option is initialized, e.g. when loading the safe parameter set, the compliance of the safety address will be checked. If no compliance exists, an initialization error is reported.
Clearly define the safety address in a drive system or plant.
Document the address in circuit diagrams and labels.
 
In drive systems with an activated safety bus, the safety address is also used as the safety bus target address. The clear assignment of the safety address must be configured in the safety PLC.
In drive systems without activated safety bus, unambiguousness and correct assignment of the safety address must be checked. For this purpose, use the
»
Easy Starter
«
or the
»
PLC Designer
«
.