Functional description
–
The drive moves at the parameterized safely limited speed SLS.
 
–
The minimum distance for the mini reference run is calculated automatically:
 
–
Minimum distance
≥
4 x tolerance window for the position comparison
 
 
–
Sequence of the plausibility check during the mini reference run:
 
1.
Are the saved position and the current position within the parameterized tolerance window for the starting position?
 
2.
Are the position value currently received from the inverter and the internal position value within the parameterized tolerance window for the position comparison?
 
3.
If the plausibility check is successful, the status bit "SHom present" is set.
 
4.
The drive changes to normal operation.
 
 
If complete homing is to be performed via the home position switch despite the "SHom present" status bit being set, the status bit must be reset with the "Clear home position" command.
Only the status bit is reset via this path. The superimposed application must start the complete reference run.