Activation
How to activate and deactivate Safe Muting:
1.
Open LSPE:
a.
»EASY Starter«: Open the +Safety parameter list+ tab.
b.
»PLC Designer«: Open the Safe parameter set object under the axis in the device tree.
2.
Click muting dialog.
The password dialog opens.
3.
Enter muting password.
The muting dialog opens.
4.
Use the displayed data to ensure that the correct inverter has been selected.
Optical device identification is activated automatically. The two LEDs "RDY" and "ERR" on the front of the selected inverter flash quickly.
5.
Start activates the function.
The function is now active for a maximum of 30 minutes. The remaining time is displayed.
6.
End function
Monitored operation is reactivated immediately.
All previously deactivated safety functions are active again.
All previously deactivated safety functions are active again.
a.
The function is automatically ended after 30 minutes.
b.
Stop ends the function manually.
c.
If the connection between LSPE and inverter is disconnected, the function is aborted immediately with an error message.