Setting
Please note when setting the parameters:
–
Defining the stop time:
 
–
Consider the closing time of the brake.
 
 
 
The mode of action of the parameters can be found in the dialog box for the function in the "Safety parameter list" in the engineering tool used.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2894:001
SS1, SS2: Stopping time
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Monitored stopping time for SS1 and SS2.
Changes only possible in the +Safety parameter list+.
0x289A
SS2 Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
Changes only possible in the +Safety parameter list+.
0
Disabled
1
Activated
0x289B:001
SS2: Mode
–
Safety parameter (+Safety parameter list+)
 
Condition at which SOS is triggered.
Changes only possible in the +Safety parameter list+.
0
SOS after stopping time
SOS is only processed after the parameterized stopping time has elapsed.
1
SOS at n=0
SOS is already triggered after reaching n=0.