Setting
Please note when setting the parameters:
–
Activate ramp monitoring.
 
–
Define the monitoring ramp:
 
–
Set the relative or absolute start offset of the ramp.
 
–
Set the smoothing time of the ramp.
The monitoring ramp is calculated from the start offset, smoothing time and stop time.
 
 
 
The mode of action of the parameters can be found in the dialog box for the function in the "Safety parameter list" in the engineering tool used.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2894:001
SS1, SS2: Stopping time
0 ... [0] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Monitored stopping time for SS1 and SS2.
Changes only possible in the +Safety parameter list+.
0x2894:002
SS1, SS2: Ramp monitoring
–
Safety parameter (+Safety parameter list+)
 
Selection of whether the deceleration ramp is to be monitored when SS1 and SS2 are executed.
Changes only possible in the +Safety parameter list+.
0
Disabled
1
Activated
0x2894:003
SS1, SS2: Ramp - Smoothing time
0 ... [0] ... 100 %
–
Safety parameter (+Safety parameter list+)
 
S-ramp time of the deceleration ramp for SS1 and SS2.
0 % = linear ramp
Changes only possible in the +Safety parameter list+.
0x2894:004
SS1, SS2: Ramp - Offset mode
–
Safety parameter (+Safety parameter list+)
 
Definition of the speed offset at the start of ramp monitoring.
Changes only possible in the +Safety parameter list+.
0
Relativ
1
Absolute
0x2894:005
SS1, SS2: Ramp - Start-offset relative
0 ... [5] ... 100 %
–
Safety parameter (+Safety parameter list+)
 
Definition of the speed offset at the start of ramp monitoring.
Changes only possible in the +Safety parameter list+.
0x2894:006
SS1, SS2: Ramp - Start-offset absolute
0 ... [0] ... 16000 rpm
–
Safety parameter (+Safety parameter list+)
 
0x2894:007
SS1, SS2: Ramp - Currently monitored speed
–
Read only: x rpm
 
–
Safety parameter (+Safety parameter list+)
 
Currently monitored speed value with active ramp monitoring.
0x2894:008
SS1, SS2: Ramp - Minimum difference
–
Read only: x rpm
 
–
Safety parameter (+Safety parameter list+)
 
Minimum difference between actual speed and monitored ramp.
0x289A
SS2 Source S-Bus
–
Safety parameter (+Safety parameter list+)
 
Selection of the safety bus as the trigger source for the function.
Changes only possible in the +Safety parameter list+.
0
Disabled
1
Activated
0x289B:001
SS2: Mode
–
Safety parameter (+Safety parameter list+)
 
Condition at which SOS is triggered.
Changes only possible in the +Safety parameter list+.
0
SOS after stopping time
SOS is only processed after the parameterized stopping time has elapsed.
1
SOS at n=0
SOS is already triggered after reaching n=0.