Analog input 2

Parameter
Address
Name / setting range / [default setting]
Information
0x2637:001
Analog input 2: Input range
Definition of the input range.
0
0 ... 10 VDC
3
-10 ... +10 VDC
4
4 ... 20 mA
5
0 ... 20 mA
0x2637:006
Analog input 2: Filter time
0 ... [10] ... 10000 ms
PT1 time constant for low-pass filter.
–
By the use of a low-pass filter, the impacts of noise to an analog signal can be minimised.
 
–
For an optimum filter effect, first the noise frequency has to be determined. The time constant then has to be set so that it equals the reciprocal value of the double frequency.
 
0x2637:007
Analog input 2: Dead band
0.0 ... [0.0] ... 100.0 %
Optional setting of a dead band that is placed symmetrically around the frequency zero point.
–
If the analog input value is within the dead band, the output value for the motor control is set to "0".
 
–
100 % = maximum value of analog input (, , )
 
–
Example: Dead band 10 % of 50 Hz: -10 V … 10 V, Dead band -5 Hz … 5 Hz, 0 V… 10 V, Dead band 0 Hz … 5 Hz
 
0x2637:010
Analog input 2: Error response
Error response for analog input 2.
–
The selected response takes place if the monitoring condition selected in is met for at least 500 ms.
 
Associated event ID:
–
537489538 | 0x20097082 - Analog input 2 fault
 
0
No response
1
Warning
2
Trouble
0x2637:013
Analog input 2: Minimum value for scaling
-200.0 ... [0.0] ... 200.0 %
0x2637:014
Analog input 2: Maximum value for scaling
-200.0 ... [100.0] ... 200.0 %