Analog input 1

Settings for analog input 1.
 
Details
The analog input 1 can be used as setpoint source.
The following settings are possible for the analog input:
–
Definition of the input range ①
 
–
Filter time for low-pass filters ②
 
–
Definition of the setting range (min/max range)③
 
–
Dead band for eliminating the smallest signal levels ④
 
–
Manual I/O control ⑤
 
Diagnostic parameters:
–
Display of the input signal status: 0x2DA4:016
 
–
24-V supply status
 
–
Calibration status
 
–
Input current status
 
–
Input voltage status
 
 
–
Display of filtered input signal in %: 0x2DA4:001
 
–
Display of setpoint in %: 0x2DA4:005
 
 
Definition of the input range
The analog input can be configured as voltage or current input. Internally, the signal is always converted to a value in percent.
 
Definition of the setting range
The setting range results from the set min and max value for the respective mode.
 
Manual I/O control
The analog input can be overridden manually. After the function is activated, the actual values are "frozen". Afterwards, each analog input can be overwritten manually.
Setting:
–
Activation: 0x263D:001
 
–
Entering the manual value: 0x263D:002
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2636:001
Analog input 1: Input range
Definition of the input range.
0
0 ... 10 VDC
3
-10 ... +10 VDC
4
4 ... 20 mA
5
0 ... 20 mA
0x2636:006
Analog input 1: Filter time
0 ... [10] ... 10000 ms
PT1 time constant for low-pass filter.
–
By the use of a low-pass filter, the impacts of noise to an analog signal can be minimised.
 
–
For an optimum filter effect, first the noise frequency has to be determined. The time constant then has to be set so that it equals the reciprocal value of the double frequency.
 
0x2636:007
Analog input 1: Dead band
0.0 ... [0.0] ... 100.0 %
Optional setting of a dead band that is placed symmetrically around the frequency zero point.
–
If the analog input value is within the dead band, the output value for the motor control is set to "0".
 
–
100 % = maximum value of analog input (, , )
 
–
Example: Dead band 10 % of 50 Hz: -10 V … 10 V, Dead band -5 Hz … 5 Hz, 0 V… 10 V, Dead band 0 Hz … 5 Hz
 
0x2636:010
Analog input 1: Error response
Error response for analog input 1.
Associated event ID:
–
537489537 | 0x20097081 - Fault - Analog input 1
 
0
No response
1
Fault > CiA402
2
Warning
0x2636:013
Analog input 1: Minimum value for scaling
-200.0 ... [0.0] ... 200.0 %
Minimum value in percent for scaling the value at the analog input (Value in percent (0x2DA4:001)).
0x2636:014
Analog input 1: Maximum value for scaling
-200.0 ... [100.0] ... 200.0 %
Maximum value in percent for scaling the value at the analog input (Value in percent (0x2DA4:001)).
0x2DA4:005
Diagnostics of analog input 1: Scaled percent value
–
Read only: x.xx %
 
Display of the actual value at the analog input, scaled with the following parameters:
–
Minimum value for scaling. 0x2636:013
 
–
Maximum value for scaling. 0x2636:014
 
0x263D:001
Analog inputs internal control: Activation
Activation of the internal control for all available analog inputs.
0
Off
1
On
0x263D:002
Analog inputs internal control: AI1 internal control
-200.00 ... [100.00] ... 200.00 %
Input of the manual value for the analog inputs.
0x263D:003
Analog inputs internal control: AI2 internal control
-200.00 ... [100.00] ... 200.00 %