Severity
The severity of an event determines the response of the inverter.
The events are logged in different places.
|
Severity
|
Response
|
Reset required
|
|
No response
|
–
The event does not trigger a response in the inverter.
–
The running process is not affected.
|
-
|
|
Information
|
–
The event does not trigger a response in the inverter.
–
The running process is not affected.
–
Logbook entry only.
|
-
|
|
Warning
|
–
The 'Warning' status is set.
–
The running process is not affected.
–
If the event is no longer active, the warning is automatically reset.
|
-
|
|
Warning locked
|
–
The 'Warning' status is set.
–
The running process is not affected.
–
If the event is no longer active, the warning must be actively reset.
|
●
|
|
Error > logbook entry only
|
–
The 'Error' status is set.
–
The running process is not affected.
–
Logbook entry only.
–
Response by external devices possible.
|
●
|
|
Error > application quick stop > quick stop
|
–
The 'Error' status is set.
–
The drive is brought to a standstill with the quick stop ramp of the application.
–
The inverter remains enabled during standstill.
|
●
|
|
Error > inverter quick stop > quick stop
|
–
The 'Error' status is set.
–
The drive is brought to a standstill with the quick stop ramp of the inverter.
–
The inverter remains enabled during standstill.
|
●
|
|
Error > inverter quick stop > inverter disabled
|
–
The 'Error' status is set.
–
The drive is brought to a standstill with the quick stop ramp of the inverter.
–
The inverter is disabled during standstill.
–
The motor has no torque.
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
|
●
|
|
Error > CiA402
|
In case of serious errors:
–
The 'Error' status is set.
–
The inverter is disabled immediately.
–
The motor has no torque.
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
|
●
|
|
In case of slight errors:
–
In 0x605E a transition response can be set.
–
The 'Fault reaction active' status is set as long as the transition response is active.
When the standstill is reached or the timeout time has expired:
–
The 'Error' status is set.
–
The inverter is disabled immediately.
–
The motor has no torque.
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
|
●
|
|
|
Error > inverter disabled
|
–
The 'Error' status is set.
–
The inverter is disabled immediately.
–
The motor has no torque.
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
|
●
|
Logging
|
Severity
|
Display in CiA status word
|
Display in event monitor
|
Display in Engineering Tool
|
Logbook entry
|
|
No response
|
-
|
0
|
-
|
-
|
|
Information
|
-
|
11
|
●
|
●
|
|
Warning
|
Bit 7 = 1
|
2
|
●
|
●
|
|
Warning locked
|
Bit 7 = 1
|
13
|
●
|
●
|
|
Error > logbook entry only
|
Bit 3 = 1
|
18
|
●
|
●
|
|
Error > application quick stop > quick stop
|
Bit 3 = 1
|
19
|
●
|
●
|
|
Error > inverter quick stop > quick stop
|
Bit 3 = 1
|
20
|
●
|
●
|
|
Error > inverter quick stop > inverter disabled
|
Bit 3 = 1
|
21
|
●
|
●
|
|
Error > CiA402
|
Bit 3 = 1
|
1
|
●
|
●
|
|
Error > inverter disabled
|
Bit 3 = 1
|
23
|
●
|
●
|