Configuring the transition response for minor faults
For slight errors, a transition response can be set before the 'Error' status is set.
Slight errors are predefined and cannot be changed by the user.
The transition response is active until standstill is reached or the timeout time has elapsed.
The inverter can still control the motor in a controlled manner.
List of defined slight errors
|
Event ID
|
Event
|
Severity
|
Configurable in
|
|
|
Fault - Motor temperature sensor
|
Warning
|
|||
|
Fault - Motor feedback
|
Fault > CiA402
|
|||
|
Motor encoder - Communication error
|
Fault > CiA402
|
|||
|
Fault - Motor holding brake
|
|
-
|
||
|
General error (see manual)
|
Fault
|
-
|
||
|
EtherCAT - Communication error
|
Fault > CiA402
|
|||
|
EtherCAT - Sync error
|
Fault
|
-
|
||
|
Sync PLL - Time-out
|
Fault
|
-
|
||
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x605E
|
CiA: Response to minor faults
|
Set the transition response for slight errors.
List of minor faults:
Configuring the transition response for minor faults |
|
|
-3
|
Advanced quick stop (hoist)
|
Behavior in case of 'Error - motor encoder':
Immediate change to the 'Error' status.
The inverter is disabled immediately.
The motor has no torque.
When the automatic brake is activated, a brake controlled by the inverter is applied.
0x2820:001 All other minor errors behave in the same way as selection -2.
|
|
|
-2
|
Advanced quick stop
|
If possible, the motor is brought to a standstill with the "quick stop" function.
If this is not possible (e.g. in the event of an encoder error), a braking torque is generated with reverse current braking or short-circuit braking.
|
|
|
0
|
No transition response
|
The motor is no longer energized.
|
|
|
2
|
Quick stop
|
The motor is brought to a standstill with the "quick stop" function.
|
|
|
0x2826
|
Timeout for error response -> quickstop
0 ... [4] ... 100 s
|
If the transition reaction specified in CiA: Response to minor faults is not completed within this time, the inverter changes to the 'Error' state.
The motor is no longer energized.
When the automatic brake is activated, a brake controlled by the inverter is applied.
0x2820:001 |
|
Configuring the transition response for minor faults