Diagnostic parameters
The inverter provides many diagnostic parameters which are helpful for operation, maintenance, error diagnosis, error correction, etc.
–
The following overview lists the most common diagnostic parameters.
–
Further parameters for more specific diagnostic purposes are described in the following subchapters.
–
The diagnostic parameters can only be read and cannot be written to.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2030
|
CRC parameter set
–
Read only
|
Display of the checksum of the parameter set.
The checksum is formed without the parameters of the technology applications.
–
Each parameter set has an individual checksum (CRC32) that is created from the settings
of all storable indices (P-flag) of the parameter set. If a setting changes,
the checksum changes as well.
–
Cyclic redundancy check (CRC):
By comparing the checksums of parameter sets, you can check
whether the parameter sets are identical or not.
–
If the checksum is identical with the checksum of the parameter set file saved in the Controller, the parameter set file does not need to be written into the inverter.
|
|
|
0x2B0B
|
Ramp generator frequency
–
Read only: x.x Hz
|
Display of the current frequency setpoint. The frequency setpoint is internally transferred to the motor control (based on scaling and ramp generator).
|
|
|
0x2D4F
|
Motor utilisation (i²xt)
–
Read only: x %
|
Display of the current thermal motor utilisation.
|
|
|
0x2DA2:001
|
Output power: Effective power
–
Read only: x.xxx kW
|
Display of the active output power for an energy analysis in the respective application.
|
|
|
0x2DA3:003
|
Output energy: Overall energy
-21474836.47 ... [0.00] ... 21474836.47 kWh
|
Display of the energy balance:
–
Positive values: Energy consumed
–
Negative values: Generated energy
0x2DA3:003 = 0 resets the energy balance.
When replacing a device, the value of the old device can be adopted as the starting value for the new device.
|
|
|
0x2DD0:001
|
Field values: Actual value
–
Read only: x %
|
Display of the actual current flow value.
|
|
|
0x2DD0:002
|
Field values: Setpoint value
–
Read only: x %
|
Display of the setpoint flow value.
|
|
|
0x2DD1:001
|
Motor currents: Actual D-current (id)
–
Read only: x.xx A
|
Display of the actual D current.
|
|
|
0x2DD1:002
|
Motor currents: Actual Q-current (iq)
–
Read only: x.xx A
|
Display of the actual Q current.
|
|
|
0x2DD1:003
|
Motor currents: Setpoint D-current (id)
–
Read only: x.xx A
|
Display of the setpoint D current.
|
|
|
0x2DD1:004
|
Motor currents: Setpoint Q-current (iq)
–
Read only: x.xx A
|
Display of the setpoint Q current.
|
|
|
0x2DD1:005
|
Motor currents: Motor current (Ieff)
–
Read only: x.xx A
|
Display of the effective motor current.
|
|
|
0x2DD2
|
Target position interpolated
–
Read only
|
Display of the interpolated position setpoint.
|
|
|
0x2DD3:001
|
Speed setpoints: Speed setpoint
–
Read only: x rpm
|
Display of the speed setpoint value 1.
|
|
|
0x2DD3:002
|
Speed setpoints: Speed setpoint 2
–
Read only: x rpm
|
Display of the speed setpoint value 2.
|
|
|
0x2DD3:003
|
Speed setpoints: Speed setpoint limited
–
Read only: x rpm
|
Display of the limited speed setpoint.
|
|
|
0x2DD4:001
|
Speed controller output signals: Output signal 1
–
Read only: x.x %
|
Display of the output signal 1 from the speed controller.
|
|
|
0x2DD4:002
|
Speed controller output signals: Output signal 2
–
Read only: x.x %
|
Display of the output signal 2 from the speed controller.
|
|
|
0x2DD6:001
|
Torque filter cascade: Starting value
–
Read only: x.x %
|
Display of the start value.
|
|
|
0x2DD6:002
|
Torque filter cascade: Notch filter 1 input value
–
Read only: x.x %
|
Display of the input value for notch filter 1.
|
|
|
0x2DD6:003
|
Torque filter cascade: Notch filter 2 input value
–
Read only: x.x %
|
Display of the input value for notch filter 2.
|
|
|
0x2DD6:004
|
Torque filter cascade: Torque setpoint filtered
–
Read only: x.x %
|
Display of the filtered torque setpoint value.
|
|
|
0x2DD7:001
|
Voltage values: Actual voltage (motor voltage limit)
–
Read only: x.x V
|
Display of the current motor voltage limit.
|
|
|
0x2DD7:002
|
Voltage values: Output signal D current controller
–
Read only: x.x V
|
Display of the output voltage of the D-current controller.
|
|
|
0x2DD7:003
|
Voltage values: Output signal Q current controller
–
Read only: x.x V
|
Display of the output voltage of the Q-current controller.
|
|
|
0x2DD7:004
|
Voltage values: D voltage (magnetisation)
–
Read only: x.x V
|
Display of the D-voltage (magnetisation).
|
|
|
0x2DD7:005
|
Voltage values: Q voltage (torque)
–
Read only: x.x V
|
Display of the Q-voltage (torque).
|
|
|
0x2DD7:006
|
Voltage values: Phases U-V
–
Read only: x.x V
|
Display of the actual voltage phase U - phase V.
|
|
|
0x2DD7:007
|
Voltage values: Phases V-W
–
Read only: x.x V
|
Display of the actual voltage phase V - phase W.
|
|
|
0x2DD7:008
|
Voltage values: Phases W-U
–
Read only: x.x V
|
Display of the actual voltage phase W - phase U.
|
|
|
0x2DD7:009
|
Voltage values: Phase U
–
Read only: x.x V
|
Display of the actual voltage of phase U.
|
|
|
0x2DD7:010
|
Voltage values: Phase V
–
Read only: x.x V
|
Display of the actual voltage of phase V.
|
|
|
0x2DD7:011
|
Voltage values: Phase W
–
Read only: x.x V
|
Display of the actual voltage of phase W.
|
|
|
0x2DDC
|
Actual slip value
–
Read only: x.x Hz
|
Display of the actual slip.
|
|
|
0x2DDD
|
Output frequency
–
Read only: x.x Hz
|
Display of the current output frequency of the inverter.
|
|
|
0x2DDE
|
Actual rotor angle position
–
Read only
|
Display of the actual position of the rotor angle.
|
|
|
0x2DDF:001
|
Axis information: Rated current
–
Read only: x.xx A
|
Display of the rated current of the axis.
|
|
|
0x2DDF:002
|
Axis information: Maximum current
–
Read only: x.xx A
|
Display of the maximum current of the axis.
|
|
|
0x2DE0:006
|
OEM service Data - SN
–
Read only
|
Display of OEM service data.
|
|
|
0x6077
|
Actual torque
–
Read only: x.x %
|
Display of the actual torque.
|
|
|
0x6078
|
Actual current
–
Read only: x.x %
|
Display of the motor actual current.
|
|
|
0x6079
|
DC-bus voltage
–
Read only: x.xxx V
|
Display of the current DC-bus voltage.
|
|