Manual setting of the motor data
There are two options to parameterize a motor.
1. Enter nameplate data
Enter the following motor data:
0x2C01:001Number of pole pairs
0x2C01:002Stator resistance
0x2C01:003Stator leakage inductance
0x2C01:004 Rated speed
0x2C01:005Rated frequency
0x2C01:006Rated power
0x2C01:007Rated voltage
0x2C01:008Cosine phi
0x2C01:009Insulation class
0x6075Rated motor currentWhen you touch the "Estimate" button in the engineering tool, more parameters depending on the motor are shown.
2. Enter data of the motor data sheet
The motor data and the parameters depending on the motor are entered. The parameters mentioned under 1. are the following:
0x2D4C:001 Thermal time constant of the winding
0x2D4C:002 Thermal time constant - laminated core
0x2D4C:003 Influence of winding
0x2D4C:004 Starting value
0x6076Rated motor torqueAdditionally for ASM:
0x2C02:001Rotor resistance
0x2C02:002Mutual inductance
0x2C02:003Magnetizing currentAdditionally for PSM:
0x2C03:001 EMF constant
0x2C03:002 Resolver pole position
0x2C03:003Temperature coefficient magnets (kTN)
0x2C03:004Encoder pole positionAfter the motor data has been parameterized via one of the two options, the following monitoring and limit values are initialized with motor-dependent preset values by touching the "Initialize" button:
0x2D44:001 Overspeed monitoring threshold
0x2D46:001 Overcurrent monitoring threshold
0x2D49:003 Motor temperature monitoring warning threshold
0x2D49:004 Motor temperature monitoring error threshold
0x6073 Maximum current
0x6075Rated motor currentParameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2822:037
|
Axis commands: Estimate all motor parameters based on rated data
|
||
|
0
|
Off/Ready
|
||
|
1
|
On/Start
|
||
|
2
|
In progress
|
||
|
3
|
Action cancelled
|
||
|
4
|
No access
|
||
|
5
|
No access (controller inhibit)
|
||
|
0x2822:038
|
Axis commands: HIPERFACE (A): Set position with synchronization
|
||
|
0
|
Off/Ready
|
||
|
1
|
On/Start
|
||
|
2
|
In progress
|
||
|
3
|
Action cancelled
|
||
|
4
|
No access
|
||
|
5
|
No access (controller inhibit)
|
||
|
0x2822:039
|
Axis commands: HIPERFACE (A): Set position with synchronization
|
||
|
0
|
Off/Ready
|
||
|
1
|
On/Start
|
||
|
2
|
In progress
|
||
|
3
|
Action cancelled
|
||
|
4
|
No access
|
||
|
5
|
No access (controller inhibit)
|
||
|
0x2C01:001
|
Motor parameters: Number of pole pairs
–
Read only
|
Display of the number of pole pairs calculated from the rated speed and rated frequency.
|
|
|
0x2C01:002
|
Motor parameters: Stator resistance
0.0000 ... [13.5000] ... 125.0000 Ω
|
General motor data.
Carry out settings as specified by manufacturer data/motor data sheet.
Note!
When you enter the motor nameplate data, take into account the phase connection implemented for the motor (star or delta connection). Only enter the data applying to the connection type selected.
|
|
|
0x2C01:003
|
Motor parameters: Stator leakage inductance
0.000 ... [51.000] ... 500.000 mH
|
||
|
0x2C01:004
|
Motor parameters: Rated speed
0 ... [4050] ... 50000 rpm
|
General motor data.
Carry out settings as specified by motor nameplate data.
Note!
When you enter the motor nameplate data, take into account the phase connection implemented for the motor (star or delta connection). Only enter the data applying to the connection type selected.
|
|
|
0x2C01:005
|
Motor parameters: Rated frequency
0.0 ... [270.0] ... 2000.0 Hz
|
||
|
0x2C01:006
|
Motor parameters: Rated power
0.00 ... [0.25] ... 655.35 kW
|
||
|
0x2C01:007
|
Motor parameters: Rated voltage
0 ... [225] ... 65535 V
|
||
|
0x2C01:008
|
Motor parameters: Cosine phi
0.00 ... [0.80] ... 1.00
|
||
|
0x2C01:009
|
Motor parameters: Insulation class
|
Insulation class of the motor (see motor nameplate).
|
|
|
0
|
Y (cut-off temperature = 90 °C)
|
||
|
1
|
A (cut-off temperature = 105 °C)
|
||
|
2
|
E (cut-off temperature = 120 °C)
|
||
|
3
|
B (cut-off temperature = 130 °C)
|
||
|
4
|
F (cut-off temperature = 155 °C)
|
||
|
5
|
H (cut-off temperature = 180 °C)
|
||
|
6
|
G (cut-off temperature > 180 °C)
|
||
|
0x2C02:001
|
Motor parameter (ASM): Rotor resistance
0.0000 ... [0.0000] ... 214748.3647 Ω
|
Equivalent circuit data required for the motor model of the asynchronous machine.
|
|
|
0x2C02:002
|
Motor parameter (ASM): Mutual inductance
0.0 ... [0.0] ... 214748364.7 mH
|
||
|
0x2C02:003
|
Motor parameter (ASM): Magnetising current
0.00 ... [0.00] ... 500.00 A
|
||
|
0x2C03:001
|
Motor parameter (PSM): Back EMF constant
0.0 ... [41.8] ... 100000.0 V/1000rpm
|
Voltage induced by the motor (rotor voltage / 1000 rpm).
For permanently excited synchronous motors, the e.m.f. constant describes the r.m.s. value of the line-to-line voltage (phase voltage) induced in idle state by the motor (reference: 1000 rpm, 20 °C).
Measured: Line to Line (L - L) |
|
|
0x2C03:002
|
Motor parameter (PSM): Resolver pole position
-179.9 ... [-90.0] ... 179.9 °
|
Equivalent circuit data required for the motor model of the synchronous machine.
|
|
|
0x2C03:003
|
Motor parameter (PSM): Magnets temperature coefficient (kTN)
-1.000 ... [-0.110] ... 0.000 %/°C
|
||
|
0x2C03:004
|
Motor parameter (PSM): Encoder pole position
-179.9 ... [0.0] ... 179.9 °
|
||
|
0x2D4C:001
|
Thermal model motor utilization (i²xt): Motor utilisation (i²xt)
1 ... [60] ... 36000 s
|
Setting of the time constant for the winding.
|
|
|
0x2D4C:002
|
Thermal model motor utilization (i²xt): Thermal time constant - laminations
1 ... [852] ... 36000 s
|
Setting of the time constant for the laminated core.
|
|
|
0x2D4C:003
|
Thermal model motor utilization (i²xt): Winding influence
0 ... [27] ... 100 %
|
Part of the thermal motor model: distribution factor of the copper winding influence.
|
|
|
0x6072
|
Max. torque
0.0 ... [250.0] ... 3276.7 %
|
–
100 % ≡ Rated motor torque 0x6076
–
The torque limitation is both effective in the static and dynamic operating points. It is used, for instance, as overload protection of the mechanical transmission path/elements, starting from the motor shaft.
–
If a value is entered here that is higher than in 0x60E0 (Positive torque limit) and 0x60E1 (Negative torque limit), the torque is limited to the lowest value.
|
|
|
0x6073
|
Max. current
0.0 ... [150.0] ... 3276.7 %
|
Max. current of the inverter.
–
100 % = Rated motor current (0x6075)
–
If the current consumption of the motor exceeds this current limit, the inverter changes its dynamic behaviour in order to counteract this exceedance.
–
If the modified dynamic behaviour fails to eliminate the excess current consumption, the inverter outputs an error.
When 0x6078 (current actual value in %) exceeds 0x6073 (max. current actual value in %) the message 0x238A is displayed.
This status is also displayed in the following network status word bits: –
0x400C:001 bit 14
–
0x400C:002 bit 2
|
|
|
0x6075
|
Rated motor current
0.001 ... [1.300] ... 1000.000 A
–
Setting can only be changed if the inverter is disabled.
|
The rated motor current that needs to be set here serves as a reference value for different parameters that involve a setting for/display of a current value in percent.
|
|
|
0x6076
|
Rated motor torque
0.001 ... [0.600] ... 100000.000 Nm
–
Setting can only be changed if the inverter is disabled.
|
The rated motor torque to be set here serves as a reference value for different parameters with a setting/display of a torque value in percent.
|
|
|
0x6080
|
Max. motor speed
0 ... [6075] ... 480000 rpm
|
Limitation of the max. motor speed. Depending on the parameter setting of 0x2D44:001 (Overspeed monitoring: threshold), the speed limitation (0x6080 / Max. motor speed) may become active before speed monitoring.
|
|