Mains voltage
The rated mains voltage set for the inverter has an impact on the operating range of the inverter.
Setting-up operation
For setup, the inverter can be operated with 15 V ... 60 V DC voltage.
–
Setting:
0x2540:001 = [4] 60 V DC (setting-up operation).
0x2540:001 = [4] 60 V DC (setting-up operation).–
Supply via DC terminal X101 (+UG/-UG).
Details
By default, the rated mains voltage is set according to the product code of the inverter.
The set rated mains voltage determines the values for fixed monitoring thresholds:
–
The error threshold and reset threshold for monitoring the DC-bus voltage
–
The voltage threshold for braking operation ("brake chopper threshold").
|
Inverter
|
Rated mains voltage 0x2540:001
|
||
|
Product code
|
Mains connection
|
Default setting
|
Required setting
|
|
i95xxxxxDxxxxxxxxx
|
230 V, 1/3-phase
|
230 Veff [0]
|
230 Veff [0]
|
|
i95xxxxxCxxxxxxxxx
|
230 V, 3-phase
|
230 Veff [0]
|
230 Veff [0]
|
|
i95xxxxxFxxxxxxxxx
|
400 V, 3-phase
|
400 Veff [1]
|
400 Veff [1]
|
|
480 V, 3-phase
|
480 Veff [2]
|
||
Check the setting of the rated mains voltage in 0x2540:001.
Make sure that this fits the supply network!
If the inverter is reset to the factory settings, the rated mains voltage is also reset to the default setting!
Voltage thresholds for monitoring the DC-bus voltage
–
The warning thresholds for monitoring are adjustable.
–
The error thresholds and reset thresholds for monitoring result from the rated mains voltage set.
|
Rated mains voltage
|
Undervoltage thresholds
|
Overvoltage thresholds
|
||||
|
Warning threshold
|
Error threshold
|
Reset threshold
|
Warning threshold
|
Error threshold
|
Reset threshold
|
|
|
Setting in
|
Setting in
|
Display in
|
Display in
|
Setting in 0x2540:005
|
Display in
|
Display in
|
Parameter