Motor temperature monitoring

In order to record and monitor the motor temperature, a PTC thermistor (single sensor according to DIN 44081 or triple sensor according to DIN 44082) or thermal contact (normally-closed contact) can be connected to the terminals T1 and T2. This measure helps to prevent the motor from being destroyed by overheating.
 
Preconditions
–
The inverter can only evaluate one PTC thermistor! Do not connect several PTC thermistors in series or parallel.
 
–
If several motors are actuated on one inverter, thermal contacts (NC contacts) (TCO) connected in series are to be used.
 
–
To achieve full motor protection, an additional temperature monitoring function with a separate evaluation must be installed.
 
–
By default, a wire jumper is installed between terminals X109/T1 and X109/T2, which must be removed when the PTC thermistor or thermal contact (TCO) is connected.
 
 
Details
If 1.6 kΩ < R < 4 kΩ at terminals X109/T1 and X109/T2, the monitoring function will be activated; see functional test below.
–
If the monitoring function is activated, the response set in 0x2D49:002 will be effected.
 
–
The setting 0x2D49:002 = 0 deactivates the monitoring function.
 
If a suitable motor temperature sensor is connected to the terminals X109/T1 and X109/T2 and the response in 0x2D49:002 is set to "Fault [3]", the response of the motor overload monitoring may be set other than "Fault [3]" in .
Motor overload monitoring (i²xt)
 
 
Functional test
Connect a fixed resistor to the PTC input:
–
R > 4 kΩ : The monitoring function must be activated.
 
–
R < 1 kΩ : The monitoring function must not be activated.
 
 
Details
If 1.6 kΩ < R < 4 kΩ at terminals X109/T1 and X109/T2, the monitoring function will be activated; see functional test below.
–
If the monitoring function is activated, the response set in 0x2D48:002 will be effected.
 
–
The setting 0x2D48:002 = 0 deactivates the monitoring function.
 
If a suitable motor temperature sensor is connected to the terminals X109/T1 and X109/T2 and the response in 0x2D48:002 is set to "Fault [3]", the response of the motor overload monitoring may be set other than "Fault [3]" in 0x2D4B:003.
Motor overload monitoring (i²xt)
 
 
Functional test
Connect a fixed resistor to the PTC input (T1/T2):
–
R > 4 kΩ : The monitoring function must be activated.
 
–
R < 1 kΩ : The monitoring function must not be activated.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D48:002
PTC temperature sensor monitoring: Error response
Setting of a response for PTC temperature monitoring.
Associated event ID:
–
537478017 | 0x20094381 - Error - Motor temperature monitoring (PTC)
 
0
No response
1
Fault > CiA402
2
Warning
0x2D49:001
Motor temperature monitoring: Temperature sensor type
Selection of the motor temperature sensor used.
0
KTY83-110
1
KTY83-110+2xPTC 150 °C
2
KTY84-130
3
Specific characteristic
4
Reserved
5
PT1000
6
PT1000+2xPTC 150 °C
0x2D49:002
Motor temperature monitoring: Response
Selection of the response to the triggering of the motor temperature monitoring.
Associated event IDs:
–
537477904 | 0x20094310 - Motor overtemperature
 
–
537478016 | 0x20094380 - Fault - Motor temperature sensor
 
–
537478018 | 0x20094382 - Motor overtemperature (load encoder/master encoder)
 
–
537478019 | 0x20094383 - Motor temperature sensor error (load encoder/master encoder)
 
0
No response
1
Warning
0x2D49:003
Motor temperature monitoring: Warning threshold
-3276.8 ... [145.0] ... 3276.7 °C
Setting of the warning threshold for motor temperature monitoring.
The warning threshold is reset with a hysteresis of 5 °C.
0x2D49:004
Motor temperature monitoring: Error threshold
-3276.8 ... [155.0] ... 3276.7 °C
Setting of the error threshold for motor temperature monitoring
The warning threshold is reset with a hysteresis of 5 °C.
0x2D49:005
Motor temperature monitoring: Actual motor temperature
–
Read only: x.x °C
 
Display of the current motor temperature.
0x2D49:006
Motor temperature monitoring: Spec. characteristic temperature grid point 1
0.0 ... [25.0] ... 255.0 °C
Parameter for the specific thermal sensor characteristic (0x2D49:001 = 3).
0x2D49:007
Motor temperature monitoring: Spec. characteristic temperature grid point 2
0.0 ... [150.0] ... 255.0 °C
0x2D49:008
Motor temperature monitoring: Spec. characteristic resistance grid point 1
0 ... [1000] ... 30000 Ω
0x2D49:009
Motor temperature monitoring: Spec. characteristic resistance grid point 2
0 ... [2225] ... 30000 Ω
0x2D49:010
Motor temperature monitoring: Temperature sensor feedback type
Selection of the thermal sensor relevant for temperature monitoring.
Selection [3] motor and load feedback: temperature monitoring responds to the highest of both temperatures of the sensors at slot A and slot B.
0
Motor encoder
3
Motor encoder and load encoder
0x2D49:011
Motor temperature monitoring: Motor temperature (Motor encoder)
–
Read only: x.x °C
 
Display of the current motor temperature measured by motor feedback.
0x2D49:012
Motor temperature monitoring: Motor temperature (load encoder)
–
Read only: x.x °C
 
Display of the current motor temperature measured by load feedback.
0x2DDF:007
Axis information: Function of X109
–
Read only
 
0
None
10
HIPERFACE DSL® (OCT)
20
PTC