Motor phase failure detection

The motor phase failure detection function can be activated for both synchronous and asynchronous motors.
 
In the Lenze setting, monitoring is not activated!
 
 
Preconditions
Motor phase failure detection during operation is suitable for applications which are operated with a constant load and speed. In other cases, transient processes or unfavourable operating points can cause erroneous triggering to occur.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2D45:001
Motor phase failure detection: Response - Motor phase 1
Selection of the response following the detection of a motor phase failure during operation.
Associated event IDs:
–
537526025 | 0x2009FF09 - Motor phase missing
 
–
537526026 | 0x2009FF0A - Motor phase failure phase U
 
–
537526027 | 0x2009FF0B - Motor phase failure phase V
 
–
537526028 | 0x2009FF0C - Motor phase failure phase W
 
0
No response
1
Fault > CiA402
2
Warning
0x2D45:002
Motor phase failure detection: Current threshold
1.0 ... [5.0] ... 10.0 %
–
100 % ≡  Maximum current 0x2DDF:002
 
–
Background: in order to be able to reliably detect the failure of a motor phase, first a certain must flow for the current sensor system. The detection function is therefore only activated if the motor current has exceeded the current threshold set here.
 
–
Display of the present motor current: 0x6078.
 
0x2D45:003
Motor phase failure detection: Voltage threshold
0.0 ... [10.0] ... 100.0 V
Voltage threshold for motor phase monitoring for the VFC control mode (0x2C00 = 6).
–
The monitoring function is triggered if the motor current exceeds the rated motor current-dependent current threshold for longer than 20 ms. Rated motor current 0x6075
 
–
In case of the V/f characteristic control, the voltage threshold is considered additionally for the motor phase failure detection. If the motor voltage is higher than the voltage threshold, monitoring is combined with the motor current.
 
0x2D45:004
Motor phase failure detection: Response - Motor phase 2
Selection of the response following the detection of a motor phase failure directly after controller enable.
Associated event IDs:
–
537526025 | 0x2009FF09 - Motor phase missing
 
–
537526026 | 0x2009FF0A - Motor phase failure phase U
 
–
537526027 | 0x2009FF0B - Motor phase failure phase V
 
–
537526028 | 0x2009FF0C - Motor phase failure phase W
 
0
No response
1
Fault > CiA402
2
Warning