Oscilloscope function

The oscilloscope function is operated via the separate "Oscilloscope" tab of the
»
EASY Starter
«
engineering tool. Here, you can find the user interface with all the relevant dialogs and setting options.
 
Preconditions
Configuring the oscilloscope and starting the recording is only possible when an online connection to the inverter has been established.
 
User interface
In the Lenze engineering tool used, set the trigger condition and the sample rate via the oscilloscope user interface when an online connection to the inverter has been established and select the parameters to be recorded.
The configuration is transferred into the inverter and checked each time it changes. Should the check identify invalid settings, the oscilloscope triggers an error message.
After the measurement is completed and when an online connection has been established, the measured data in the inverter is transmitted to the engineering tool and represented graphically on the oscilloscope user interface.
 
A
Oscilloscope toolbar
E
Set trigger conditions
B
Oscillogram field
F
Set sample rate and time base
C
Channel list field
G
Start / stop of recording
D
Status line
H
Comment input field and error message
 
 
Toolbar
Icon
Function
Load oscillogram / configuration from file
Load recorded oscillogram from the device
Save oscillogram in file
Copy oscillogram to the clipboard
Print oscillogram
Display cursor
Center cursor
Scale curve automatically
Activate zoom function
"Time base:"
Display of the set time base
Tool settings (right-hand side of the toolbar)
 
Technical data
Number of channels
1 ... 8
Data memory depth
Maximally 65535 measured values for each channel
Data width of a channel
Maximally 64 bits, according to the data type of the parameter to be recorded
Sample rate
62.5 
µ
s or a multiple thereof, max. 100 ms
Recording duration at lowest sampe rate
4.1 s (62.5 
µ
s * 65535 measured values)
Recording duration at highest sample rate
6553,5 s (100 ms * 65535 measured values)
Maximum time base
655,35 s
Trigger level
According to the value range of the parameter to be triggered
Trigger delay
-100 % ... +400 %
Trigger source
Channel 1 ... 8
 
Selecting parameters to be recorded
The oscilloscope supports up to eight channels, thus maximally eight parameters can be recorded in an oscillogram. The Channels list field serves to configure the parameters to be recorded as signal sources:
Column
Name
Meaning
1
-
Curve colour for the representation in the oscillogram
2
Ch
Channel number
3
On
on / off
4
Inv
Inversion on / off
5
Name
Selection of the parameter to be recorded
6
yPos I
Value at cursor I in vertical direction
7
yPos II
Value at cursor II in vertical direction
8
| ΔyPos |
Difference between the two values of yPos I and yPos II (displayed as amount)
9
Unit
Scaling
10
AS
Activation / deactivation of the autoscaling function
11
1 / Div
12
Offset
The offset value is subtracted from the recorded raw value before the scaling is executed. This serves to, e. g., make very small value fluctuations visible within one consistently very high recording value (e. g. harmonics with a low amplitude).
13
Position
Regarding the vertical curve scale -5 ... 5, the position value determines the vertical position of the zero point of the Y axis of a curve.
 
How to select a parameter for recording:
1.
Double-click the "Name" column in the Channel list field to open the "Selection of signal sources" dialog box.
 
2.
Select the parameters to be recorded in the dialog box.
 
3.
Press the "Ok" button. This closes the dialog box and the selection is accepted.
 
4.
Repeat the steps 1 ... 3 to select up to seven further parameters to be recorded.
 
The selected parameters are recorded when the oscilloscope is started.

How to change a parameter for recording:
1.
Double-click the parameter to be changed in the Channels list field in the "Name" column.
 
2.
Make a new selection in the "Selection of signal sources" dialog box.
 
3.
Press the "Ok" button. This closes the dialog box and the selection is accepted.
 
The changed parameters are recorded when the oscilloscope is started.

How to cancel a selection again:
1.
Right-click the parameter to be removed in the Channels list field in the "Name" column to open the context menu.
 
2.
Select the "Remove signal source" command in the context menu.
 
 
Defining the recording time / sample rate
How to define the duration and sample rate for recording:
1.
Select the desired time base in the time base list field.
 
a.
The current setting of the time base multiplied by 10 results in the recording time.
 
b.
As the size of the measured data memory in the inverter is limited, a compromise is usually made between sample rate and recording time.
 
2.
Either enter the desired sample rate in [ms] in the sample rate input field or open the "Sample rate selection" dialog by clicking the "Sample rate" button and select a sample rate < 1 ms.
 
a.
The sample rate in the inverter is automatically corrected to integer multiples of 62.5
µ
s.
 
Thus, the duration and sample rate are defined for recording.
 
Defining the trigger condition
Based on the trigger condition, define the starting time of recording in the inverter. The oscilloscope offers various trigger conditions which serve to control the recording of the measured values.
The trigger threshold can be changed in the "Value" input field on the "Settings" tab if the channel is selected in "Signal source" that contains the corresponding parameter.
Setting
Function
Signal source
Selection of the trigger source:
Channel
Triggering takes place on a channel configured in the "vertical channel settings" list field.
immediate trigger
No trigger condition, recording takes place immediately after the start.
Value
Value, from which onwards triggering is caused.
Deceleration
Time delay of recording with regard to the trigger event.
Pre-trigger
When entering a negative delay time, you can detect signals that occur before the trigger event.
The trigger time is marked with a dashed line in the oscillogram.
If it is triggered on the occurrence of an event, values caused by the event can be detected in this way.
Post-trigger
When entering a positive delay time, you can detect signals that occur a certain time after the trigger event.
Edge
Two trigger types are available:
increasing
First, the value must fall below the defined trigger value and then exceed it in order that triggering is activated.
decreasing
First, the value must exceed the defined trigger value and then fall below it in order that triggering is activated.
 
Starting recording
Press the button , "Start recording"
 
In order to obtain a sample rate as high as possible when the parameter values are recorded, the data is first saved in the measured data memory of the inverter and then transmitted to the Engineering PC as oscillogram. The current recording status is displayed in the status bar.
 
Adjusting the representation
As soon as the diagram does not show the complete measurement anymore, a scrollbar appears below the time axis. You can use the scrollbar to move the visible section horizontally. The time-axis inscription and the position indicator are automatically corrected during scrolling.
 
After recording and subsequent transmission of the online oscillogram to the Engineering PC, it is visualised in the oscilloscope. If required, you can now adjust the representation using the zoom function or the automatic scaling function.
Change time base subsequently
A measurement already carried out can be extended or compressed by changing the time base.
For this purpose, change the setting of the time base via the toolbar (on top).
 
Zoom function
The zoom function will be activated by selecting the in the toolbar. When the function is activated, the button is highlighted.
Zoom function
Proceeding
Zoom selection
Hold down the left mouse button and draw the section to be zoomed:
–
The selection is shown with a frame.
 
–
When the left mouse button is released, the selection is zoomed in the oscillogram.
 
Horizontal stretching
On the horizontal scale:
Hold down the left mouse button and move the mouse pointer to the left to stretch the shown selection from the right edge.
Hold down the right mouse button and move the mouse pointer to the right to stretch the shown selection from the left edge.
Moving the mouse pointer in opposite direction continuously reduces the stretching.
Vertical stretching
On the vertical scale:
Hold down the left mouse button and move the mouse pointer to the bottom to stretch the shown selection from the top.
Hold down the right mouse button and move the mouse pointer to the top to stretch the shown selection from the bottom.
Moving the mouse pointer in opposite direction continuously reduces the stretching.
Return to original representation
Click the right mouse button in the diagram to return step by step to the original representation.
 
Automatic scaling function
Use the automatic scaling function to automatically scale and reposition the representation of selectable signal characteristics in the oscillograph and reset the offset to "0".
How to execute automatic scaling
1.
Select the channels and parameters for automatic scaling in the Channels dialog box.
 
2.
Click the corresponding symbol in the oscilloscope toolbar to activate the automatic scaling function.
 
 
The cursor function
In addition to the zoom and scaling function, there is the cursor function which is called by double-clicking the Channels list field.
The double-click opens a list of all signal sources with the following options:
–
Display of individual measured values of a selectable channel
 
–
Addition, subtraction or multiplication of any two measured values
 
–
Square-law mean value of any two measured values
 
How to use the cursor function:
1.
Go to the oscilloscope toolbar and click the "Cursor" button to activate the cursor function.
 
a.
Two movable vertical measuring lines are displayed in the oscillogram.
 
2.
Select the channel for which individual measuring lines are to be displayed from the Channels list field.
 
3.
Hold down the left mouse button and drag the red vertical measuring line to the desired position.
 
a.
The active measuring line is represented by a continuous line, the inactive measuring line is represented by a dotted line.
 
b.
If you position the mouse pointer over the inactive measuring line, the measuring line automatically becomes active.
 
c.
The columns yPos I and yPos II in the Channels list field display the values measured at the measuring lines. The column ΔyPos or QWM displays the cursor differential value or square-law mean value of all values between both cursors.
 
d.
The sum value to be displayed can be defined in the "tool settings" dialog. This dialog can be set via the "Tool settings" dialog on the right in the toolbar.
 
e.
Comparing peak values: Several values displayed in the oscillogram can be compared to each other using a horizontal measuring line. The measuring line is automatically created based on the current cursor point and thus cannot be shifted.
 
 
Managing oscillograms
If several data records are loaded in the oscilloscope at the same time, the measured data to be displayed is selected via the respective tab above the displayed oscillogram. There are three types of oscillograms:
–
Device oscillogram
The device oscillogram is the only oscillogram to establish a connection to the target system in order to carry out an oscilloscope measurement. It is always displayed as the first "Device on the left" tab.
 
–
Offline oscillogram
The offline oscillogram is an oscillogram already saved in the Engineering PC.
 
–
The configuration of the offline oscillogram can be reused for future recordings.
 
–
The offline oscillogram is displayed as a tab with the file name that was allocated for this oscillogram while being saved.
 
 
–
Merge oscillogram
The merge oscillogram ("Merge" tab) is automatically available if two or more oscillograms are loaded in the oscilloscope at the same time.
 
–
In the merge oscillogram, several characteristics from the currently loaded oscillograms can be overlaid, e. g. to compare signal characteristics from different recordings.
 
 
 
Commenting oscillograms
You can add a comment on the selected oscillogram into the comment input field.
–
When you execute the "Save oscillogram" command, the comment is saved together with the oscillogram in the file.
 
–
When you select an oscillogram with a comment to be loaded in the "Load oscillogram" dialog box, this comment is displayed in the dialog box.
 
 
Saving oscillogram in file
After selecting the parameters to be recorded from the selection list of the signal sources and making any further necessary settings, you can save this configuration and the recording if already carried out on the Engineering PC for a later reuse.
How to save the oscillogram:
1.
Click the symbol in the toolbar. the "Save oscillogram" dialog box is displayed.
 
2.
Define a name in the Name input field of the oscillogram to be saved.
 
3.
Click the "Export to file" button.
 
4.
Specify the folder and file name for the oscillogram be stored in the Save as dialog box.
 
5.
Click the Save button. The dialog box is closed.
 
The current oscillogram is saved.
 
Loading oscillogram / configuration from file
The reuse of a saved configuration is only reasonable for inverters of the same type, as otherwise due to a scaling of the oscilloscope channels that is not adapted, incorrect values are displayed!
 
Data sets/configurations which have already been saved can be reloaded into the oscilloscope any time, e.g. for the overlay function.
How to load an oscillogram or a configuration:
1.
Click the symbol in the oscilloscope toolbar. The "Load oscillogram" dialog box is displayed.
 
2.
Press the Search... button.
 
3.
Select the file to be imported within the desktop environment from the Open dialog box.
 
4.
If the oscillogram is to be used as configuration, select the As configuration... option.
 
5.
Click the Open button. The dialog box is closed.
 
The selected oscillogram or configuration is imported.
 
Closing the oscillogram
You can close an open OFFLINE oscillogram again any time.
–
After an oscillogram is closed, it is no longer available in the oscillogram list field. The oscilloscope changes automatically to the display of the ONLINE oscillogram.
 
–
If the closed oscillogram was included in the MERGE oscillogram, its channels will be removed from the MERGE oscillogram.
 
–
Go to the oscilloscope toolbar and click the symbol to close the currently displayed OFFLINE oscillogram.
 
 
Overlay function
The overlay function serves to overlay several characteristics from the currently loaded data sets, e.g. to compare signal characteristics from different recordings.
–
If two or more oscillograms are loaded in the oscilloscope, e.g. the ONLINE oscillogram and an oscillogram that was previously loaded into a file, a "MERGE" oscillogram will be automatically available in the "Oscillogram" list field.
 
–
If the merge oscillogram is selected, the desired characteristics to be overlaid or compared can be selected from the loaded oscillograms in the Vertical channel settings group field.
 
–
If an ONLINE oscillogram is used in the MERGE oscillogram, an update is carried out in the MERGE oscillogram in the case of a renewed recording.
 
–
Removing variables from an OFFLINE or ONLINE oscillogram causes the characteristics in the MERGE oscillogram to be deleted.
 
 
Copying an oscillogram to the clipboard
For documentation purposes, it is possible to copy the measured data of an oscillogram as a table or, alternatively, the oscilloscope user interface as a picture, to the clipboard for use in other programs.
How to copy the oscillogram to the clipboard:
1.
Click the symbol in the oscilloscope toolbar. The "Copy oscillogram" dialog box is displayed.
 
2.
Select the desired option:
 
a.
Curve points: the measured data is copied to the clipboard as a table.
 
b.
Screenshot: the oscilloscope user interface is copied to the clipboard as a picture.
 
3.
Press the OK button. The dialog box is closed and the selected option is copied to the clipboard.