Brake energy management
When braking electrical motors, the kinetic energy of the drive train is fed back regeneratively to the DC bus. This energy causes a DC-bus voltage boost. If the energy fed back is too high, the inverter reports an error.
Several different strategies can serve to avoid DC-bus overvoltage:
–
Stopping the deceleration ramp function generator when the active voltage threshold for the brake operation is exceeded
–
Use of the "Inverter motor brake" function
–
Combination of the above named options
Details
The voltage threshold for braking operation results on the basis of the rated mains voltage set:
|
Rated mains voltage (0x2540:001)
|
Voltage thresholds for braking operation
|
|
|
Braking operation on
|
Braking operation off
|
|
|
230 V
|
390 V DC
|
380 V DC
|
|
400 V
|
725 V DC
|
710 V DC
|
|
480 V
|
780 V DC
|
765 V DC
|