Use of a brake resistor
For braking operation, optionally the brake chopper integrated in the inverter (brake transistor) can be used.
NOTICE
Incorrect dimensioning of the brake resistor may result in the destruction of the integrated brake chopper (brake transistor).
▶
Only connect a brake resistor complying in terms of performance to terminals RB1 and RB2 of the inverter.
▶
Avoiding thermal overload of the brake resistor.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2550:001
|
Brake resistor: Minimum resistance
–
Read only: x.x Ω
|
Display of the minimum brake resistance value that can be used.
|
|
|
0x2550:002
|
Brake resistor: Resistance value
0.0 ... [180.0] ... 500.0 Ω
|
Resistance value of the brake resistor connected.
–
The value to be entered can be obtained from the brake resistor nameplate.
|
|
|
0x2550:003
|
Brake resistor: Rated power
0 ... [5600] ... 800000 W
|
Rated power of the brake resistor connected.
–
The value to be entered can be obtained from the brake resistor nameplate.
|
|
|
0x2550:004
|
Brake resistor: Maximum thermal load
0 ... [485] ... 1000000 kWs
|
Thermal capacity of the brake resistor connected.
–
The value to be entered can be obtained from the brake resistor nameplate.
|
|
|
0x2550:006
|
Brake resistor: Reference resistance
|
Reference value for the calculation of brake chopper utilization.
|
|
|
0
|
Minimum resistance
|
||
|
1
|
Resistance value
|
||
|
0x2550:007
|
Brake resistor: Thermal load
–
Read only: x.x %
|
Display of the utilisation of the brake resistor connected.
|
|
|
0x2550:008
|
Brake resistor: Warning threshold
50.0 ... [90.0] ... 150.0 %
|
Warning threshold for brake resistor monitoring.
–
If the utilisation shown in reaches the threshold set, the response selected in 0x2550:010 is effected.
–
The warning is reset with a hysteresis of 20 %.
|
|
|
0x2550:010
|
Brake resistor: Response to warning
|
Selection of the response that is executed when the warning threshold for brake resistor monitoring is reached.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Warning
|
||
|
0x2550:011
|
Brake resistor: Response to error
|
Selection of the response to be executed when the error threshold for brake resistor monitoring is reached.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Warning
|
||
Severity