Safe Muting (MUT)
|
Function included in variant:
|
|
|
Extended Safety
|
(From standard device firmware V1.3, safety firmware V1.1 with parameter set version V1.1)
This function deactivates selected safe inputs and all functions of the safety bus.
"Safe Muting" is used to move the drive even if the inverter is in a safety state.
–
The function may only be used during commissioning or for maintenance work.
–
The function is active for a maximum of 30 minutes.
–
It can be ended at any time.