Sensor inputs

Contact function test
An internal contact function test is carried out at the safe inputs.
 
Safe input in the ON state
–
A LOW level on a channel sets the input to the OFF state; discrepancy monitoring starts at the same time.
 
–
A LOW level must be detected on both channels within the discrepancy time; if it is not, a discrepancy error is reported.
 
–
In order to be able to acknowledge a discrepancy error, a LOW level must previously have been detected on both channels.
 
Safe input in the OFF state
–
A HIGH level on a channel triggers discrepancy monitoring.
 
–
A HIGH level must be detected on both channels within the discrepancy time; if it is not, a discrepancy error is reported.
 
–
To be able to acknowledge the discrepancy error, a HIGH level must be detected before at both channels.
 
 
Fig. 1: Contact function test − state behavior
 
Fig. 2: Contact function test − error-free input signals
Fig. 3: Contact function test – faulty input signals
A, B
Safe input, channel A and channel B 
 
C
Internal valuation of the safe input 
 
D
Discrepancy monitoring 
 
AIE
Error acknowledgement 
 
①
Discrepancy monitoring active 
 
②
Discrepancy monitoring time-out 
 
③
Error acknowledgement impermissible 
 
④
Error acknowledgement permissible 
 
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2118:001
SD-In: SD-In1 sensor type
–
Safety parameter (+Safety parameter list+)
 
Configure or deactivate safe input as active or passive input.
0
Input disabled
1
Passive sensor
2
Active sensor
0x2118:002
SD-In: SD-In2 sensor type
–
Safety parameter (+Safety parameter list+)
 
Configure or deactivate safe input as active or passive input.
0
Input disabled
1
Passive sensor
2
Active sensor
0x2118:003
SD-In: SD-In3 sensor type
–
Safety parameter (+Safety parameter list+)
 
Configure or deactivate safe input as active or passive input.
0
Input disabled
1
Passive sensor
2
Active sensor
0x2118:004
SD-In: SD-In4 sensor type
–
Safety parameter (+Safety parameter list+)
 
Configure or deactivate safe input as active or passive input.
0
Input disabled
1
Passive sensor
2
Active sensor
0x2119:001
SD-In: SD-In1 discrepancy time
0 ... [1000] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
Maximum time within which the two channels of the secure input may be in impermissible states without an error being detected..
0x2119:002
SD-In: SD-In2 discrepancy time
0 ... [10] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
0x2119:003
SD-In: SD-In3 discrepancy time
0 ... [10] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
0x2119:004
SD-In: SD-In4 discrepancy time
0 ... [10] ... 30000 ms
–
Safety parameter (+Safety parameter list+)
 
0x211A:001
SD-In: SD-In1 input delay
0 ... [0] ... 100 ms
–
Safety parameter (+Safety parameter list+)
 
Delay time between the detection of the signal change at the safe input and the effective evaluation of the input signal.
0x211A:002
SD-In: SD-In2 input delay
0 ... [0] ... 100 ms
–
Safety parameter (+Safety parameter list+)
 
0x211A:003
SD-In: SD-In3 input delay
0 ... [0] ... 100 ms
–
Safety parameter (+Safety parameter list+)
 
0x211A:004
SD-In: SD-In4 input delay
0 ... [0] ... 100 ms
–
Safety parameter (+Safety parameter list+)
 
0x211B
Input image
–
Read only
 
Bit-coded display of the status of the safe inputs
Logic: 1 = channel/input active
Bit  0
SD-In1 channel A
Bit  1
SD-In1 channel B
Bit  2
SD-In2 channel A
Bit  3
SD-In2 channel B
Bit  4
SD-In3 channel A
Bit  5
SD-In3 channel B
Bit  6
SD-In4 channel A
Bit  7
SD-In4 channel B
Bit  16
AIE
Bit  17
AIS
Bit  24
IRS
Bit  25
IRL
Bit  31
Button S82