Analog inputs and outputs

The following parameters serve to diagnose the analog inputs and outputs of the inverter.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2DA4:001
Diagnostics of analog input 1: Value in percent
–
Read only: x.x %
 
Display of the current input value at X3/AI1 scaled as value in percent.
–
100 % = 10 V or 20 mA or 5 V
 
0x2DA4:016
Diagnostics of analog input 1: Status
–
Read only
 
Bit coded display of the status of analog input 1 (X3/AI1).
Bit  0
Mode 0: 0 ... 10 VDC active
Bit  3
Mode 3: -10 ... 10 VDC active
Bit  4
Mode 4: 4 ... 20 mA active
Bit  5
Mode 5: 0 ... 20 mA active
Bit  6
24 V supply OK
Bit  7
Calibration successful
Bit  9
Input current too low (mode 4)
Bit  10
Input voltage too low (mode 2)
Bit  11
Input voltage too high (mode 4)
 
Related topics
Configure analog inputs