Severity

The severity of an event determines the response of the inverter.
The events are logged in different places.
 
Severity
Response
Reset required
No response
–
The event does not trigger a response in the inverter.
 
–
The running process is not affected.
 
-
Information
–
The event does not trigger a response in the inverter.
 
–
The running process is not affected.
 
–
Logbook entry only.
 
-
Warning
–
The 'Warning' status is set.
 
–
The running process is not affected.
 
–
If the event is no longer active, the warning is automatically reset.
 
-
Warning locked
–
The 'Warning' status is set.
 
–
The running process is not affected.
 
–
If the event is no longer active, the warning must be actively reset.
 
●
Error > logbook entry only
–
The 'Error' status is set.
 
–
The running process is not affected.
 
–
Logbook entry only.
 
–
Response by external devices possible.
 
●
Error > application quick stop > quick stop
–
The 'Error' status is set.
 
–
The drive is brought to a standstill with the quick stop ramp of the application.
 
–
The inverter remains enabled during standstill.
 
●
Error > inverter quick stop > quick stop
–
The 'Error' status is set.
 
–
The drive is brought to a standstill with the quick stop ramp of the inverter.
 
–
The inverter remains enabled during standstill.
 
●
Error > inverter quick stop > inverter disabled
–
The 'Error' status is set.
 
–
The drive is brought to a standstill with the quick stop ramp of the inverter.
 
–
The inverter is disabled during standstill.
 
–
The motor has no torque.
 
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
 
●
Error > CiA402
In case of serious errors:
–
The 'Error' status is set.
 
–
The inverter is disabled immediately.
 
–
The motor has no torque.
 
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
 
●
In case of slight errors:
–
In 0x605E a transition response can be set.
 
–
The 'Fault reaction active' status is set as long as the transition response is active.
 
When the standstill is reached or the timeout time has expired:
–
The 'Error' status is set.
 
–
The inverter is disabled immediately.
 
–
The motor has no torque.
 
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
 
●
Error > inverter disabled
–
The 'Error' status is set.
 
–
The inverter is disabled immediately.
 
–
The motor has no torque.
 
–
When the automatic brake is activated, a brake controlled by the inverter is applied.
 
●
 
Logging
Severity
Display in CiA status word
0x6041
Display in event monitor
Display in Engineering Tool
Logbook entry
No response
-
0
-
-
Information
-
11
●
●
Warning
Bit 7 = 1
2
●
●
Warning locked
Bit 7 = 1
13
●
●
Error > logbook entry only
Bit 3 = 1
18
●
●
Error > application quick stop > quick stop
Bit 3 = 1
19
●
●
Error > inverter quick stop > quick stop
Bit 3 = 1
20
●
●
Error > inverter quick stop > inverter disabled
Bit 3 = 1
21
●
●
Error > CiA402
Bit 3 = 1
1
●
●
Error > inverter disabled
Bit 3 = 1
23
●
●