Extended Safety - Parameter set plausibility errors

The following table contains the detailed information about the possible plausibility errors.
The error code corresponds to the entry in 0x2115:005.
 
Error information 1
0x2115:005
Error in the setting of the safe parameterization
1
If SD-In1 is deactivated, SD-In1 must not be parameterized as a source for any function.
2
If SD-In2 is deactivated, SD-In2 must not be parameterized as a source for any function.
3
If SD-In3 is deactivated, SD-In3 must not be parameterized as a source for any function.
4
If SD-In4 is deactivated, SD-In4 must not be parameterized as a source for any function.
5
If no safety bus is parameterized, no S-Bus bit may be parameterized as source for a function.
6
If no motor encoder is parameterized, no function requiring an encoder may be parameterized.
7
If cascading is parameterized:
–
SD-In4 must be parameterized as an active sensor.
 
–
SSE must be parameterized to STO via SD-In4.
 
–
The input delay for SD-In4 must be ≤10 ms.
 
–
The restart after STO must be "acknowledged".
 
–
SD-Out1 must not be controlled via S-Bus.
 
8
If a resolver is parameterized as motor encoder, max. 10000 rpm divided by the number of pole pairs of the resolver may be set as speed value due to the system.
9
If SS1 is parameterized so that STO is triggered after reaching n = 0, the delay time "STO after n = 0" must be less than or equal to the stopping time.
10
If OMS is used via the S-Bus, "OMS: Function at LOW level" must be equal to "Normal operation", because a level inversion on the S-Bus has no effect.
11
If OMS is used via S-Bus, at least one stop function must also be parameterized via S-Bus to switch to the safe state in the event of bus failure.
12
If no motor encoder system is parameterized, the delay time "STO after n = 0" must be zero.
13
The lower position limit for PDSS must be less than or equal to the upper position limit for PDSS.
14
The lower SCS limit for PDSS must be less than or equal to the upper SCS limit.
15
The lower position limit for SLP must be less than or equal to the upper position limit for SLP.
16
The lower position limit for SCA must be less than or equal to the upper position limit for SCA.
17
The lower diagnostic position for SHom must be less than or equal to the upper diagnostic position.
18
If the parameterized value for the maximum compensated slip is not zero, it must be less than or equal to the tolerance of the position comparison.
19
If the input source for SHom_Start is deactivated, no function based on an absolute position may be parameterized.
23
If the input source for the SHom diagnostic positions is not deactivated, the lower diagnostic position must be less than or equal to the upper diagnostic position.
If PDSS is also used, the lower diagnostic position must be greater than the lower position limit and lower SCS limit.
24
If the input source for the SHom diagnostic positions is not deactivated, the upper diagnostic position must be greater than or equal to the lower diagnostic position.
If PDSS is also used, the upper diagnostic position must be smaller than the upper position limit and upper SCS limit.
25
If no motor encoder system is parameterized, no load encoder system may be parameterized either.
26
If no load encoder system is parameterized, the gearbox factors for numerator and denominator must be set to default values (100).
The load encoder mounting direction must be parameterized with the setting "Same as motor encoder".
27
If muting (MUT) is parameterized, a password must be assigned.
Valid from safety parameter set V1.1.
29
If the S-Bus is to be hidden via muting (MUT), an S-Bus must also be parameterized.
Valid from safety parameter set V1.1.
30
If SD-In1 is to be hidden via muting (MUT), SD-In1 must also be parameterized.
Valid from safety parameter set V1.1.
31
If SD-In2 is to be hidden via muting (MUT), SD-In2 must also be parameterized.
Valid from safety parameter set V1.1.
32
If SD-In3 is to be hidden via muting (MUT), SD-In3 must also be parameterized.
Valid from safety parameter set V1.1.
33
If SD-In4 is to be hidden via muting (MUT), SD-In4 must also be parameterized.
Valid from safety parameter set V1.1.
34
If the parameter set version is smaller than V1.1, only 0 ... 4 may be set for the S-Bus configuration.
Valid from safety parameter set V1.0.
35
If SD-In1 is deactivated, SD-In1 must not be parameterized for SBC as source.
Valid from safety parameter set V1.1.
36
If SD-In2 is deactivated, SD-In2 must not be parameterized for SBC as source.
Valid from safety parameter set V1.1.
37
If SD-In3 is deactivated, SD-In3 must not be parameterized for SBC as source.
Valid from safety parameter set V1.1.
38
If SD-In4 is deactivated, SD-In4 must not be parameterized for SBC as source.
Valid from safety parameter set V1.1.
39
If no safety bus is parameterized, the S-Bus bit must not be parameterized as a source for SBC.
Valid from safety parameter set V1.1.
40
The tolerance window of the diagnostic positions must lie completely within the displayable position range.
41
If the parameter set version is smaller than V1.2, only 0, 4 or 11 may be set for the S-Bus configuration.
Valid from safety parameter set >V1.1.
42
If the parameter set version is smaller than V1.3, only 0, 1 or 2 may be set for the motor encoder configuration.
Valid from safety parameter set >V1.2.
43
If the parameter set version is smaller than V1.3, the gearbox factor denominator may only be set to max. 100.
Valid from safety parameter set >V1.2.
44
If the parameter set version is smaller than V1.3, the gearbox factor counter may only be set between 20 ... 50000 may be set.
Valid from safety parameter set >V1.2.