Inverter diagnostics

The following parameters supply some information about the current operating status of the inverter.
 
This includes the following information:
–
Active access protection after log-in by means of PIN1/PIN2
 
–
Currently loaded parameter settings
 
–
Cause(s) for disable, quick stop and stop.
 
–
Active control source and active setpoint source
 
–
Active operating mode
 
–
Status of the internal motor control
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2010:001
Device event monitor: EreignisortEvent location
–
Read only
 
Display of the event location for the currently pending event.
0
No error
1
Functional safety
4
Basic settings
5
Communication
6
Kinematics
7
Motion
8
Technology application
0x2010:002
Device event monitor: Severity
–
Read only
 
Display of the severity level for the currently active event.
0
No response
1
Fault > CiA402
2
Warning
11
Information
13
Warning locked
15
Trouble > only logbook entry
16
Trouble
18
Fault > only logbook entry
19
Fault > application quick stop > quick stop
20
Fault > inverter quick stop > quick stop
21
Fault > inverter quick stop > inverter disabled
23
Fault > inverter disabled
0x2010:003
Device event monitor: Event status
–
Read only
 
Display of the event status for the currently pending event.
0
No event active
1
Reset possible
2
Reset not possible
0x2010:005
Device event monitor: Number of current event
–
Read only
 
Display of the event ID for the currently pending event.
Bit  0
0x2010:006
Device event monitor: Time stamp of current event
–
Read only: x ns
 
Display of the time stamp for the current upcoming event.
0x2012:001
Device information: SD card status
–
Read only
 
0
No SD card connected
1
SD card connected
0x2012:002
Device information: Application Credit available
–
Read only
 
0x2013:001
Application information: Active application
–
Read only
 
0
CiA 402
1
"CiA 402 advanced" technology application
5
"AC Drive Profile" technology application
10
"Speed Control" technology application
20
"Table Positioning" technology application
40
"Electronic Gearbox" technology application
41
"Sync and Correction" technology application
50
"Winder Dancer" technology application
51
"Winder Tension" technology application
100
"User" technology application
0x2013:002
Application information: Application Credit required
–
Read only
 
0x2040
Access protection status
–
Read only
 
Bit-coded display of the active access protection after login by PIN1/PIN2.
Bit  0
No write access
Bit  1
Only favorites changeable
0x2539:001
Hardware-Diagnose: External supply voltage
–
Read only: x.x V
 
0x2539:002
Hardware-Diagnose: Control board temperature
–
Read only: x.x °C
 
0x2823
Status of axis commands
–
Read only
 
0x282A:001
Status words: Cause of disable
–
Read only
 
Bit-coded display of the cause(s) for disabled inverter.
Bit  2
Axis command
1 = the inverter was disabled via axis command 0x2822:001.
Bit  7
Drive not ready
1 = the inverter was disabled internally since the drive was not ready for operation.
Possible causes:
–
Under/overvoltage in the DC bus
 
–
Defective device hardware
 
Bit  12
CiA402 Inverter disabled
1 = the inverter was disabled by the internal state machine.
The bit is only set if
–
Operating mode 0x6060 = "CiA: Velocity mode (vl) [2]" and
 
–
state machine in the "Switch on disabled" state and
 
–
the state change has not been carried out via the "Disable operation" command.
 
Bit  14
Safety
1 = the inverter has been disabled by the integrated safety system.
Bit  16
PROFINET energy pause active
-
0x282A:004
Status words: Extended status word
–
Read only
 
Bit-coded status word.
Bit  0
Brake is opened
-
Bit  1
Reserved
0x2831
Inverter status word
–
Read only
 
Bit coded status word of the internal motor control.
Bit  0
Position controller in limitation
-
Bit  1
Speed setpoint 1 limited
1 = input of speed controller 1 in limitation.
Bit  2
Speed controller in limitation
1 = output of speed controller 1 in limitation.
Bit  3
Torque setpoint limited
1 = setpoint torque in limitation.
Bit  4
Q-current setpoint limited
1 = setpoint current in limitation.
Bit  5
Speed setpoint 2 limited
1 = input of speed controller
2 in "torque mode" in limitation.
Bit  6
Upper speed limit active
1 = in "torque mode", the speed is limited to upper
speed limit 0x2946:001
.
Bit  7
Lower speed limit active
1 = in "torque mode", the speed is limited to lower
speed limit 0x2946:002
.
Bit  8
Flying restart active
-
Bit  9
Flying restart completed
Bit  10
Output frequency limited
1 = setpoint frequency with V/f operation in limitation.
Bit  11
Magnetization completed
1 = Magnetisation completed during V/f operation.
Otherwise 0.
Bit  12
Motor phase error
1 = motor phase failure detection active.
Bit  13
Feedback open circuit
-
Bit  14
Error reset blocking time active
1 = the error can only be reset when the blocking time has elapsed.
Bit  15
Clamp active
-
0x2833
Inverter status word 2
–
Read only
 
Bit-coded status word 2 of the inverter.
Bit  0
Motor encoder modified
Bit  1
Manual test mode active
1 = manual test mode active.
Bit  2
Manual control active
1 = manual control active.
Bit  4
Motor encoder = absolute value encoder
-
Bit  5
Motor encoder absolute position available
Bit  6
DC braking active
1 = DC braking
active.
Bit  7
Motor encoder angle drift invalid
-
Bit  8
Load encoder modified
Bit  9
Load encoder angle drift invalid
Bit  10
Load encoder = absolute value encoder
Bit  11
Load encoder absolute position available
Bit  12
Brake open
Bit  13
Cable check active
Bit  14
Mains failure detected
0x284F
Current error
–
Read only
 
Test display of the current error.
–
This object contains a reference for the text to be displayed from the ESI file as well as the substitution values for all wildcards in this text.
 
–
The text has the same structure as the diagnostic messages in the history buffer.
 
0x603F
Error code
–
Read only
 
Error message
Bit  0